12
Vendor Information – Huntner Fans
12.1 Yaskawa Modbus RTU or Modbus TCP/IP Mappings to BACnet, Metasys N2 and Modbus RTU
Point Name
Com Status
CommandXXX
SpeedCmdXXX
SpeedMonXXX
FaultMonXXX
FanXXX/CommLossTimeout
FanXXX/Current
FanXXX/FireRelay
FanXXX/FireRelayFunction
FanXXX/FreqRefSel
FanXXX/ip1
FanXXX/ip2
FanXXX/ip3
FanXXX/ip4
FanXXX/RunCmdSel
FanXXX/sn1
FanXXX/sn2
FanXXX/sn3
FanXXX/sn4
FanXXX/Write
12.2 Mitsubishi Modbus RTU or Modbus TCP/IP Mappings to BACnet, Metasys N2 and Modbus RTU
Point Name
Com Status
InvXXX Inverter Reset
InvXXX Parameter Clear
InvXXX All Parameter Clear
InvXXX Parameter Clear
InvXXX All Parameter Clear
InvXXX Inverter Status Run/Stop
InvXXX Inverter Status Forward Rot
InvXXX Inverter Status Reverse Rot
InvXXX Inverter Status SL/RH
InvXXX Inverter Status OL/RM
InvXXX Inverter Status IPF/RL
InvXXX Inverter Status FU/JOG
InvXXX Inverter Status ABC1/RT
InvXXX Inverter Status ABC2/AU
InvXXX Inverter Status CS
InvXXX Inverter Status MRS
InvXXX Inverter Status STOP
55
BACnet
BACnet
Object
Object ID
Type
BI
0
AV
1
AV
2
AI
3
AI
4
AV
5
AI
6
BI
7
AV
8
AV
9
AV
10
AV
11
AV
12
AV
13
AV
14
AV
15
AV
16
AV
17
AV
18
AV
19
BACnet
BACnet
Object
Object ID
Type
BI
0
AV
1
AV
2
AV
3
AV
4
AV
5
BV
6
BV
7
BV
8
BV
9
BV
10
BV
11
BV
12
BV
13
BV
14
BV
15
BV
16
BV
17
Hunter Fans ProtoNode FPC-N64
N2 Data
N2 Address
Type
DI
1
AO
1
AO
2
AI
3
AI
4
AO
5
AI
6
DI
7
AO
8
AO
9
AO
10
AO
11
AO
12
AO
13
AO
14
AO
15
AO
16
AO
17
AO
18
AO
19
N2 Data
N2 Address
Type
DI
1
AO
1
AO
2
AO
3
AO
4
AO
5
DO
6
DO
7
DO
8
DO
9
DO
10
DO
11
DO
12
DO
13
DO
14
DO
15
DO
16
DO
17
Modbus Register
1
1
2
65
128
1012
8199
43.2
1024
384
997
998
999
1000
385
1001
1002
1003
1004
2304
Modbus Register
10001
40002
40003
40004
40006
40007
40009.0
40009.1
40009.2
40009.3
40009.4
40009.5
40009.6
40009.7
40009.8
40009.9
40009.10
40009.11