Electrical Characteristics - Fujitsu ARU18RGLX Design & Technical Manual

Hide thumbs Also See for ARU18RGLX:
Table of Contents

Advertisement

10. Electrical characteristics

Item
Voltage
Power
supply
Frequency
1
MCA *
Starting current
MAX. CKT. BKR *
Power cable
Wiring spec.
2
*
Connection
4
cable *
*1: Minimum Circuit Ampacity (Calculation based on UL1995)
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Maximum Circuit Breaker
*4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
Unit
V
Hz
A
A
3
A
AWG
Size
AWG
Limited wiring
ft (m)
length
Model name
AOU18RGLX AOU24RGLX AOU30RGLX AOU36RGLX
18.3
6.6
9.6
20
- 100 -
208/230~
60
20.8
24.6
11.5
16.1
30
16—14
20—16
167 (51)
10. Electrical characteristics