Carrier Bryant 575J 07 Series Installation, Start-Up And Service Instructions Manual page 37

Heat pump condensing units with puron refrigerant
Table of Contents

Advertisement

Puron (R-410A) refrigerant operates at 50 percent to
70 percent higher pressures than R-22. Be sure that servic-
ing equipment and replacement components are designed
to operate with Puron refrigerant.
Puron refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be
400 psig, DOT 4BA400 or DOT BW400.
Puron systems should be charged with liquid refrigerant.
Use a commercial type metering device in the manifold
hose when charging into suction line with compressor
operating.
Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low-side retard.
Use hoses with 700 psig service pressure rating.
Leak detectors should be designed to detect HFC
refrigerant.
Puron refrigerant, as with other HFCs, is only compatible
with POE oils.
Vacuum pumps will not remove moisture from oil.
Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
Do not install a suction-line filter drier in liquid-line.
POE oils absorb moisture rapidly. Do not expose oil to
atmosphere.
UNIT
575J*07G/H
575J*08M/N
575J*12G/H
APPENDIX A — AIR CONDITIONER AND
HEAT PUMP WITH PURON
QUICK REFERENCE GUIDE
APPENDIX B — WIRING DIAGRAM LIST
COOLING
STAGES
CHARACTERISTICS
2
2
2
®
POE oils may cause damage to certain plastics and roofing
materials.
Wrap all filter driers and service valves with wet cloth
when brazing.
A factory approved, liquid-line filter drier is required on
every unit.
Do not use an R-22 TXV.
If indoor unit is equipped with a TXV, it must be changed
to a Puron refrigerant TXV.
Never open system to atmosphere while it is under a
vacuum.
When system must be opened for service, recover refriger-
ant, break vacuum with dry nitrogen before opening
system.
Always replace filter drier after opening system for
service.
Do not vent Puron refrigerant into the atmosphere.
Do not use capillary tube coils.
Observe all warnings, cautions, and bold text.
All Puron refrigerant heat pumps must have indoor TXV.
Do not leave Puron refrigerant suction line driers in place
for more than 72 hours.
ELECTRICAL
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
37
DIAGRAM
PAGE
NUMBER
NUMBER
38AU000443
38AU000444
38AU501316
38AU501315
38AU501317
38AU000445
38AU000446
38
39
40
41
42
43
44