Carrier Bryant 575J 07 Series Installation, Start-Up And Service Instructions Manual page 16

Heat pump condensing units with puron refrigerant
Table of Contents

Advertisement

NOMINAL
POWER
SUPPLY
c,d
UNIT
V-Ph-Hz
208/230-3-60
575J*07G/H
460-3-60
575-3-60
208/230-3-60
575J*08M/N
460-3-60
575-3-60
208/230-3-60
575J*12G/H
460-3-60
575-3-60
NOMINAL
POWER
SUPPLY
c,d
UNIT
V-Ph-Hz
208/230-3-60
575J*07G/H
460-3-60
575-3-60
208/230-3-60
575J*08M/N
460-3-60
575-3-60
208/230-3-60
575J*12G/H
460-3-60
575-3-60
NOTE(S):
a. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit
shall be fuse. Canadian units may be fuse or circuit breaker.
b. Motor RLA and LRA values are established in accordance with Underwriters Laboratories (UL) Standard 1995.
c. The 575-v units are UL, Canada-listed only.
d. Unbalanced 3-Phase Supply Voltage: Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the formula below to determine the
percentage of voltage imbalance.
e. The MCA values are calculated in accordance with The NEC. Article 440.
max voltage deviation from average voltage
% Voltage
= 100 x
Imbalance
Example: Supply voltage is 230-3-60
AB = 224 v
A
B
C
BC = 231 v
AC = 226 v
MOTOR
(224 + 231 + 226)
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
Table 11 — Electrical Data — 575J*07-12 60 Hz Units
COMPRESSOR
VOLTAGE
RANGE
No. 1
Min
Max
RLA
187
253
17.5
414
506
8.4
518
633
6.3
187
253
27.4
414
506
12.9
518
633
10.0
187
253
15.9
414
506
7.7
518
633
5.7
COMPRESSOR
VOLTAGE
RANGE
No. 1
Min
Max
RLA
187
253
17.5
414
506
8.4
518
633
6.3
187
253
27.4
414
506
12.9
518
633
10.0
187
253
15.9
414
506
7.7
518
633
5.7
average voltage
681
=
=
227
3
3
4
= 1.78%
227
No. 2
OFM (ea)
LRA
RLA
LRA
Qty
136
2
66
2
55
2
164
2
94
2
65
2
110
15.6
110
2
52
7.7
52
2
39
5.8
39
2
No. 2
OFM (ea)
LRA
RLA
LRA
Qty
136
2
66
2
55
2
164
2
94
2
65
2
110
15.6
110
2
52
7.7
52
2
39
5.8
39
2
LEGEND
BRKR
FLA
LRA
MCA
NEC
PWRD CO —
RLA
UNPWR CO —
16
a,b
WITHOUT POWERED CONVENIENCE OUTLET
Power Supply
Fuse or
FLA
MCA
HACR
e
Brkr
1.5
25/25
30/30
0.8
13
20
0.7
10
15
1.5
38/38
60/60
0.8
18
30
0.7
14
20
1.5
39/39
50/50
0.8
19
25
0.7
15
20
WITH POWERED CONVENIENCE OUTLET
Power Supply
Fuse or
FLA
MCA
HACR
e
Brkr
1.5
30/30
45/45
0.8
15
20
0.7
11
15
1.5
43/43
60/60
0.8
20
30
0.7
16
25
1.5
44/44
50/50
0.8
22
25
0.7
17
20
Circuit Breaker
Full Load Amps
Locked Rotor Amps
Minimum Circuit Amps Protection
National Electrical Code
Powered Convenience Outlet
Rated Load Amps
Unpowered Convenience Outlet
Disconnect Size
FLA
LRA
24/24
142/142
12
70
9
59
35/35
170/170
17
98
13
69
40/40
226/226
20
108
15
82
Disconnect Size
FLA
LRA
29/29
147/147
14
72
11
61
40/40
175/175
19
100
15
71
45/45
231/231
22
110
17
84