40
EBN853 / EBN861 ELECTRONIC UNIT | OI/EBN853/EBN861/EX-EN REV. C
... 11 Repair

Fuses

Type
Fuse
EBN853
External fuse
Mains fuse
Analog input
Brake fuse
DC link fuse
Heater (optional)
EBN861
External fuse*
Brake fuse
DC link fuse
Fuse for binary outputs (3x)
Heater (optional)
*
The 35 A safety fuse and the 16 A thermal circuit breaker are included in the scope of delivery. The conductor cross-section between the fuse and the electronic
system must be at least 2.5 mm
Change from one to two columns
Installation location
External
Connection area
Connection area
Power supply board
Power supply board
Connection area
External
Power supply board
Power supply board
Connection area
Connection area
2
(14 AWG).
Design
Rated current of fuse
at 115 V AC
16 A, time-lag
G-fuse cartridge
12.5 A, time-lag
5 × 20 mm
G-fuse cartridge
40 mA, fast-acting
5 × 20 mm
G-fuse cartridge
0.315 A, medium time-lag 0.315 A, medium time-lag
5 × 20 mm
G-fuse cartridge
10 A, super fast-acting
6.3 × 32 mm
G-fuse cartridge
2 A, time-lag
5 × 20 mm
Safety fuse / thermal
circuit breaker
G-fuse cartridge
5 × 20 mm
G-fuse cartridge
6.3 × 32 mm
G-fuse cartridge
5 × 20 mm
G-fuse cartridge
2 A, time-lag
5 × 20 mm
at 230 V AC
16 A, time-lag
10 A, time-lag
40 mA, fast-acting
10 A, super fast-acting
2 A, time-lag
35 A / 16 A
0.315 A, medium time-lag
16 A, super fast-acting
0.2 A, medium time-lag
2 A, time-lag

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebn853

Table of Contents