Display Settings; Heater Information - A.O. Smith 101 Series Instruction Manual

Hide thumbs Also See for 101 Series:
Table of Contents

Advertisement

display settings

description/action
Select Display Settings from the main menu and press the
Operational Button under "SELECT" to enter this menu. This
menu contains adjustable display options for viewing information
on the Uim's LCD screen. Use the Up & Down Buttons to
navigate the menu.
• temperature units - Adjustable user setting that changes
temperature units display to Celsius °C or Fahrenheit °F.
• Backlight delay - Adjustable user setting that determines
how long the Uim's LCD backlight remains illuminated after
a key has been pressed. Available settings are; Always Off,
10, 30 or 60 seconds and Always On.
• contrast - Adjustable user setting to adjust the Uim's LCD
screen contrast between text and background.
note: These settings are adjusted in the same way
described for the Operating Set Point And Differential
Adjustment on page 45.

heater information

description/action
Select Heater information from the main menu and press the
Operational Button under "SELECT" to enter this menu. This
menu contains non adjustable operational information.
• elapsed time - Total accumulated time the control system
(water heater) has been energized.
• Burner on time - Total accumulated time the control
system has been in the heating operating state; burner run
time.
• cycle count - Total accumulated count of heating cycles.
• ccB Version - Software version for central control board.
• uim Version - Software version for user interface module.
note: Historical data is stored in the CCB's memory. if this
CCB is replaced during servicing the historical data on the
CCB being replaced will be lost. The data stored in the new
circuit board will no longer reflect the entire history of the
water heater.
The Elapsed Time, Burner On Time and Cycle Count indicate
age, usage and wear.
if the Cycle Count per day is high (divide cycle count by
days to determine cycles per day) or the cycle duration is
short (determine burner on time total minutes, divide burner
on time total minutes by cycle count) consider rasing the
Differential setting to avoid short cycling and excessive
component wear, see Operating Set Point And Differential
Adjustment on page 45.
This historical data can also be used to assist facilities
managers in forecasting planned replacement of equipment
to help avoid lengthy and costly hot water supply interruptions.
Display Settings
Temperature Units
Backlight Delay
Contrast
CHANGE
Heater Information
Elapsed Time
Burner On Time
Cycle Count
CCB Version
UIM Version
CHANGE
47
display
°F
30s
60%
BACK
HELP
display
10 day 0 hrs 0 mins
5 hrs 22 mins
00000035
X.XX
X.XX
BACK
HELP