Troubleshooting Guide I
Are there any signals present or sources which could cause the
current behavior?
Check if any sources around causing big electromagnetic fields.
Check if any sources around causing distortion on power supply.
Main fuse
Check on WP models if main fuse is still OK.
External fail-safe power supply
Check if 24 V DC is present and stable.
Check if 24 V DC is stable during actuator movement.
External 24 V DC Fail-Safe Power Supply
2
2
PE
SUPPLY, 24 V DC 1) 2)
General check of wiring
Check if everything is wired correctly according to wiring diagram.
Check if there is any loose or damaged cable visible.
Mechanical connection valve to actuator
Check if flange and bushing is mounted properly.
Check if there is no misalignment on extensions or brackets.
Checking Mechanical Connection
Section 1: Troubleshooting Guide I