2.6.2 Hi-Therma Monobloc
High
For compressor
Low
Fuse capacity on PCB6 (F201)
CCP timer
Setting time
For electric heater
For water circulation
For water temperature
For refrigerant temperature
For the control circuit
MODEL
Pressure switches
Cut-out
Cut-in
Cut-out
Cut-in
1~ 230V 50Hz
MODEL
Safety thermostat
Fuse capacity
Low water pressure switch
Low water pressure
Condition 1
High water pressure
Condition 1
Low water flow control
Activation
Water pump control
High temperature protection
Freeze temperature protection
Freeze temperature protection
Condition 1
Condition 2
Condition 3
Fuse capacity
MPa
MPa
A
-
min
Pw<0.3Bar for 180 seconds
Pw≥4.0Bar for 180 seconds
Water flow control by Water pump feedback
(Reset manual by Alarm)
3
44: 0.5m
/h 60-80: 0.6m
Water Pump status by feedback control
+5°C of Maximum water temperature (Heating mode)
-2°C of minimum water temperature (Cooling mode)
(Tl<-4°C and Tg<8°C) or (Tg≤1°C )for 240 seconds
(Tl<-4°C and Tg<8°C) or (Tg≤1°C )for60 seconds
Tl+Two≤4°C and Tl≤1 for 180 seconds
10A (Inside PCB1,EFR1)
17
General data
AHZ-044/080HCDS1
Automatic reset, non-adjustable
(Each one for each compressor)
4.4±0.15
3.40±0.2
0.05±0.03
0.15±0.03
30
Non adjustable
3
AHZ-044/080HCDS1
——
20
Automatic Reset
3
/h