Outdoor Fan Motor Control - Toshiba RAS-B22PKVSG-TR Service Manual

Table of Contents

Advertisement

Item
3. Outdoor fan
The blowing air volume at the outdoor unit side is controlled.
motor control
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
* For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
Air conditioner ON
(Remote controller)
Indoor unit controller
1) Outdoor unit
operation command
(Outdoor fan control)
2) Fan speed ≥ 400.
when the motor OFF.
(by strong wind)
Fan motor ON
3) Fan lock
4) Motor operates as shown in the table below.
Cooling Operation
Model Name
RAS‐22PAVSG‐E,‐TR
Hz < 13.8
RAS‐24PAVSG‐E,‐TR
Hz < 13.8
Fan Speed Ranges
Min
To  38C
f6
To  28C
f5
To  15C
3 f
To
To  5.5C
f2
To  0C
1 f
To < 0C
1 f
When To is abnormal OFF
Outdoor Fan Speeds (rpm)
Tap RAS‐22PAVSG‐E,‐TR RAS‐24PAVSG‐E,‐TR
f1
200
f2
300
f3
300
f4
360
f5
440
f6
500
f7
550
f8
600
Operation flow and applicable data, etc.
Fan motor OFF continues
YES
(Use wind for heat
NO
YES
Air conditioner
NO
Compressor Speeds (rps)
13.8  Hz < 30.6
30.6  Hz
13.8  Hz < 32.4
32.4  Hz
Max
Min
Max
Min
fB
f8
fE
fA
fA
7 f
fE
9 f
7 f
5 f
9 f
f7
f5
f4
f7
f6
3 f
3 f
5 f
4 f
2 f
2 f
4 f
3 f
fB
OFF
fE
f1
Tap RAS‐22PAVSG‐E,‐TR RAS‐24PAVSG‐E,‐TR
250
f9
300
fA
350
fB
450
fC
500
fD
560
fE
600
fF
650
exchanging)
Alarm
OFF
display
Model Name
RAS‐22PAVSG‐E,‐TR
RAS‐24PAVSG‐E,‐TR
Max
To  10C
 <
 
fE
T
o 10C
To
 <
 
fE
T
o 5C
 <
 ‐
fB
T
o
3C
f9
When To is abnormal
f7
f5
fE
Outdoor Fan Speeds (rpm)
650
700
700
700
750
700
800
750
850
750
950
900
950
900
- 36 -
FILE NO. SVM-18033
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the
fan motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
Heating Operation
Compressor Speeds (rps)
Hz < 13.8
13.8  Hz < 30.6
30.6  Hz
Hz < 13.8
13.8  Hz < 32.4
32.4  Hz
7 f
8 f
f9
fB
E f
E f
E f
E f
fF
fF
f9
fE
fE
fE
fF