8.5

Air damper adjustment

The air damper is set in factory. This regulation is purely indica-
tive.
Each installation however, has its own unpredictable working
conditions: actual nozzle output; positive or negative pressure in
the combustion-chamber, the need of excess air, etc.
All these conditions may require a different air damper setting.
8.5.1

Only for code 3518465 - 3514260

The air setting is performed by mean of two independent damp-
ers (see Fig. 16 and Fig. 17).
Main air damper (A) - Fig. 16
The main air damper can be set in either of two positions. To set
the positions of the damper, proceed as follows:
 Remove the secondary air damper (B) loosing the screws 1).
 Loosen the screw 2) and rotate the main air damper (A) to
the required position.
 Retighten the screw 2) and put back the secondary air
damper (B).
8.6

Electrodes setting

The position of the electrodes cannot be regulat-
ed. In case of failure, check that the measure-
ments as shown on the figure are respected.
WARNING
Before removing or assembling the nozzle, loosen the screw (A,
Fig. 18) and move the electrodes ahead.
2903310
Start-up, calibration and operation of the burner
4 ±
0.3 mm
D5230
20
GB
A
2
D7532
A
2 - 2.5
B
1
Fig. 16
mm
Fig. 18