Goodman Amana ComfortNet GMVC8 Service Instructions Manual page 87

80% communicating gas furnaces
Table of Contents

Advertisement

SERVICING
PRESSURE SWITCH CHART
Model
*MVC80604B*AA
*MVC80805C*AA
*MVC80805C*BA / BB
*MVC81005C*AA
*MVC81005C*BA / BB
ADVC80603B*AA / BA / BB
ADVC80703BXAA
ADVC80805C*AA
ADVC80805C*BA / BB
ADVC80905CXAA
ADVC81005C*AA
ADVC81005CNBA
ADVC81005CXBA
ADVC81005C*BB
ADVC81155CXAA
*MVC8 / ADVC8 Pressure Switch Trip Points And Usage Chart
Low Fire
Low Fire
Set Point on
Max Make
Pressure Fall
Pressure On
(PF) W.C.
Rise W.C.
- 0.35 ± .05
- 0.54
- 0.30 ± .05
- 0.49
- 0.35 ± .05
- 0.54
- 0.30 ± .05
- 0.49
- 0.30 ± .05
- 0.45
- 0.30 ± .05
- 0.45
- 0.30 ± .05
- 0.45
- 0.30 ± .05
- 0.45
- 0.35 ± .05
- 0.54
- 0.30 ± .05
- 0.45
- 0.30 ± .05
- 0.45
- 0.35 ± .05
- 0.54
- 0.30 ± .05
- 0.45
- 0.35 ± .05
- 0.54
- 0.30 ± .05
- 0.45
High Fire
High Fire
Set Point on
Max Make
Pressure Fall
Pressure On
(PF) W.C.
Rise W.C.
- 0.65 ± .05
- 0.84
- 060 ± .05
- 0.79
- 0.65 ± .05
- 0.84
- 060 ± .05
- 0.79
- 0.55 ± .05
- 0.70
- 0.55 ± .05
- 0.70
- 0.55 ± .05
- 0.70
- 0.55 ± .05
- 0.70
- 0.65 ± .05
- 0.84
- 0.55 ± .05
- 0.70
- 0.55 ± .05
- 0.70
- 0.65 ± .05
- 0.84
- 0.55 ± .05
- 0.70
- 0.65 ± .05
- 0.84
- 0.55 ± .05
- 0.70
Low / High
Pressure Switch
Assembly
Part #
0130F00049
0130F00050
0130F00049
0130F00050
B1370210
B1370210
B1370210
B1370210
0130F00049
B1370210
B1370210
0130F00049
B1370210
0130F00049
B1370210
87