Interfaces; Leds - Toshiba 288V Installation And Operation Manual

Scib energy storage system
Table of Contents

Advertisement

10

Interfaces

10.1

LEDS

Each SCiB ESS cabinet has three LEDS which is controlled by each system host controller. The three LED indicators are:
1. Battery Ready (Green) – The light will come on when the batteries have reached certain State of Charge (SOC) set-
point. The light will blink if the batteries are charging but have not reached the pre-determined SOC setpoint. (See
table for more information.)
2. Discharging (Amber) – The light will come on when the UPS system is in discharge mode and the batteries are pro-
viding power to the UPS. The light will start to blink when the battery voltage has reached 98% of the cutoff voltage to
indicate the UPS system is fixing to shutdown. (See table for more information.)
3. Fault (Red) – The fault light will come on if the host controller determines there is an issue with the system. The light
will come on initially when the system is started up and turn off when the battery breaker is closed if there are no other
faults present. The light will be steady for any fault that the system can't recover from but will blink if the system can
recover from the fault. For example, loss of communication will cause the light to blink but will go off if communication
recovers. (See table for more information.)
The following table describes the front panel LED behaviors and the associated meaning.
Condition
Initializing/Waiting for
Charging
Control Power supplied.
Waiting for contactor
closure.
Battery Charging. Volt-
age is less than Startup
Voltage (<280V)
Battery Charging.
Voltage is greater than
Startup Voltage. (>280V)
Discharging and DC
voltage is above 4% of
Cutoff Voltage. (<280V)
Discharging and DC
voltage is within 4% of
Cutoff Voltage. (<223V)
Loss of communication
Host to Host (CN5 PCB
90700) loss of
communication.
288V SCiB Energy Storage System Installation and Operation Manual – 203810-000
TABLE 10.1 – 1:
LED STATUS
Battery
Discharging
Ready
Scanning Between Green, Amber, and Red
Scanning Between Green
and Amber
Blinking
(On 1 sec,
Off
Off 1 sec)
On
Off
Steady
Off
On Steady
Off
Blinking
Blinking
Blinking
On
Off
Steady
LED STATUS BEHAVIOR
Affects
System
Fault
or Unit
Unit
Off
Unit
Off
Unit
Off
Unit
Off
Unit
Off
Unit
Blink 8 times
every 5
Unit
Seconds
Blink One
Time Every 5
System
Seconds
Description
Sequence control, blink ready then discharge
then fault back to ready. While the contactors are
waiting to close stay in this state
First state when starting up UPS System.
No action needed.
Battery is charging and hasn't reached full
capacity yet. No Faults detected.
Battery has reached full capacity and is on stand
by. No Faults detected.
Battery is discharging and has more than 2%
capacity remaining.
Battery is discharging and is nearly depleted
Loss of communication between host controller
and BMU or Abnormal BMU. Contact Toshiba
Field Service if problem persists.
General Communication Error.
29