Installation; Installation General; Placing The Appliance - ubbink Ubiflux Vigor W400 Installation Regulations

Hide thumbs Also See for Ubiflux Vigor W400:
Table of Contents

Advertisement

5 Installation

5.1 Installation general

Installing the appliance:
1. Placing the appliance (®
2. Connecting the siphon and condensate discharge (®
3. Connecting the air ducts (®
4. Electrical connections (®
The installation and installing should meet the following requirements:
▪ Quality requirements of ventilation systems in homes, ISSO 61.
▪ Quality requirements of balanced ventilation dwellings, ISSO 62
▪ Regulations regarding the ventilation of homes and residential.
▪ Safety provisions for low-voltage installations
▪ The regulations for connecting indoor plumbing in homes and residential buildings.
▪ Any additional regulations of the local power companies
▪ The installation regulations of the Ubiflux Vigor W400 appliance.
▪ In addition to the above design and installation requirements and recommendations, the national building and
ventilation regulations must be respected.

5.2 Placing the appliance

The Ubiflux Vigor W400 (Plus) appliance can be mounted onto the wall with the supplied mounting bracket. For a
vibration-free installation, the appliance must be mounted to a solid wall with a minimum mass of 170 kg/m
gypsum block or metal stud wall does not suffice! Additional measures such as double panelling or extra studs
are required in that case. On request, a mounting support for floor mounting (with the same minimal mass) is
available.
In addition, the following aspects must be taken into account:
▪ The appliance must be installed in an insulated frost-free room (> 10 °C), in order to, for example, prevent
freezing of the condensate discharge
▪ The appliance must be placed level.
▪ The appliance must not be placed in a room with a high level of condensation (such as a bathroom).
▪ In order to prevent condensation on the outside of the appliance, the installation room must be ventilated.
▪ The installation room must be able to provide a condensate discharge with a sufficient water seal and drop for
the condensed water.
▪ Newly built houses with a lot of moisture from the construction work need to be ventilated in a natural manner
before being put to use.
▪ Make sure there is a free space of at least 70 cm at the front of the appliance and a free headroom of 1.8 m.
▪ Make sure there is a free space of at least 25 cm above the appliance, for connecting the appliance and any
necessary servicing of the circuit board. The ambient temperaturehas to be between +10 °C and + 40 °C.
Placing the appliance
page 13 )
Connecting air ducts
Electrical connections
Ubiflux Vigor W400 615912-D
Connecting the condensate discharge
page 15)
page 16)
page 14)
2
. A
Ubbink / 13