④ The following table for the torque required to tighten the nuts.
Table 5
Thickness of
Pipe diameter
copper tube
Φ6.35 mm
≥0.8 mm
Φ9.52 mm
≥0.8 mm
Φ12.7 mm
≥0.8 mm
Φ15.9 mm
≥1.0 mm
Φ19.05 mm
≥1.0 mm
-------------------------------------------------------------------------------------------------------------------------
Caution!
 During the connection of the indoor unit and BU module to the refrigerant pipe, never pull any
joints of the indoor unit and the BU module by force; otherwise the capillary pipe or other pipe
may crack, which then would result in leakage.
 The refrigerant pipe should be supported by brackets, that is, don't let the unit withstand the
weight of it.
 For the Super Free Match system, each pipe should be labeled to tell which system it belongs to
avoid mistaken inaccurate piping.
-------------------------------------------------------------------------------------------------------------------------
6.5

Connection of Refrigerant Pipe

Tightening
torque
15~30 N· m
35~40 N· m
45~50 N· m
60~65 N· m
70~75 N· m