Remote Iserver; Figure 4.21 Configuration Menu - Remote Iserver - Omega iServer DPi8 User Manual

Embedded ethernet for iseries monitor/controller
Hide thumbs Also See for iServer DPi8:
Table of Contents

Advertisement

4.12.1 Remote iServer

It's recommended to configure the Remote iServer and have it up and running before the
Local iServer is configured.
1.
A static IP address must be assigned to the Remote iServer. This means that the DHCP
must remain disabled. Refer to the DHCP section of the user's manual for details.
2.
Use a browser to access the Remote iServer's WEB page. Simply type the iServer's
IP address at the browser's URL location (i.e. 192.168.1.50) followed by an Enter key.
You should then see the iServer's main WEB page.
3.
Click on the Update button.
4.
Click on Configuration, you will be prompted with a Password (default is 12345678).
5.
On the Configuration page, under Serial Communication section, make sure the
parameters such as Baud Rate, Data Bits, Parity, Stop Bits, Flow Control, etc. match
with your attached serial device.
6.
Make sure to set the End Character (Hex) to 0D and the Timeout to 500.
7.
Under Terminal Server section, set Number of Connections to 1 or higher.
8.
Click on Save button for the changes to take place.
Make sure that the serial cable and communication settings between the iServer and the
serial device are valid.
Figure 4.21
shows the valid
values that
need to be set
in the Remote iServer.
The Baud Rate, Data
Bits, Parity, Stop Bits,
Flow Control, and
Transceiver values
depend on what the
serial device supports.
CONFIGURATION
http://192.168.1.50
Address
Baud Rate 9600
Flow Control none
End Character (Hex) 0D Forward End Char enable
TCP/UDP TCP
Connection Ctrl not used
Remote Access disable

Figure 4.21 Configuration Menu - Remote iServer

CONFIGURATION
Serial Communication
Data Bit 7 Bits
Transciever RS-485
Serial Port Password disable
Terminal Server
Server Type slave
Number of Connections 1
Device No. 1
Remote Access (Tunneling)
Remote IP Address 0.0.0.0
Save Reset
Main Menu
31
Parity odd
Stop Bits 1 bit
Modbus/TCP disable
Timeout 0500 msecs
1234abcd
Local Port 02000
Connection Timeout 00100 msecs
Remote Port 02000