4.5.4 Configuration

• This section explains the Configuration page of the iServers's Web interface.
• When connecting your device to the iServer, the Serial Communications parameters
must match, between the iServer and your serial device.
CONFIGURATION
http://192.168.1.200
Address
Baud Rate 9600
Flow Control none
A
End Character (Hex) 0D Forward End Char enable
B
TCP/UDP TCP
Connection Ctrl not used
C
Remote Access disable
4.5.4.A Serial Communication
Baud Rate: The speed on the serial port and can be set from 300 to 115,200 bits/s
(default is 9600 bits/s.)
Data Bit: Options are 7 or 8 (default is 7 bits.)
Parity: Options are Odd, Even, and None (default is Odd.)
Stop Bits: Options are 1 and 2 bits (default is 1 bit.)
Flow Control: Options are Software Flow Control (Xon/Xoff), Hardware Flow Control
(CTS/RTS), and None (default is None.)
CONFIGURATION
Serial Communication
Data Bit 7 Bits
Transciever RS-485
Serial Port Password disable
Terminal Server
Server Type slave
Device No. 1
Remote Access (Tunneling)
Remote IP Address 0.0.0.0
Save Reset
Figure 4.10 Configuration
Parity odd
Modbus/TCP disable
Timeout 0500 msecs
1234abcd
Number of Connections 0
Connection Timeout 00100 msecs
Main Menu
18
Stop Bits 1 bit
Local Port 02000
Remote Port 02000