Possible Problems At Commissioning; Operational Checks - Carrier 38ZS/ZF Installation, Operation And Maintenance Instructions

Air-cooled condensing units with axial fan and free vertical discharge
Table of Contents

Advertisement

9 - COMMISSIONING
● Verify the absence of any leaks of the refrigerant. In case of
a leak:
- Completely drain the refrigerant charge using a specifi c
recovery machine for R-410A and repair the leak.
- Next, reload the refrigerant into the unit according to charge
data provided in a table of the chapter on "Maintenance"
and in the unit's data plate.
- Add the refrigerant via the charging valve using the
appropriate equipment and tools, with the compressors
stopped, monitoring the pressures to control any anomaly.

9.2 Possible problems at commissioning

All indications given in this manual must be respected and
complied with to guarantee a correct operation of the units.
Next, several possible operation problems are stated which
could happen if the conditions of the commissioning are not
appropriate.
● Air fl ow lack: very high diff erences between inlet and outlet
temperatures, originated by a high pressure drop in the ducts,
or by other causes that impede the correct circulation.
● Air recirculation in the unit, originated by some obstacle in the
air aspiration or outlet.
● Noise problems because of excessive air fl ow in the grille.
● Water overfl owing to the pan problems, originated by an
excessive fl ow, an incorrect siphon installation or because a
defective unit level.
● Refrigerant circuit humidity problem, because of an incorrect
vacuum realization.

9.3 Operational checks

Check the unit operation by verifying the electronic control and
the safety devices.
It is also recommendable to create a report, taking note of the
date, which includes the following information:
● the nominal voltage,
● current absorbed by the compressors, fans and other electrical
components,
● signifi cant temperatures in the cooling circuit (see attached
table),
● other aspects considered interesting such as alarms detected
by the electronic control of the unit.
The recording of these parameters whilst the unit is running
allows controlling the installation performance and it is the
best possible way to avoid breakdowns since the analysis of
these data makes early detection of anomalies possible or the
provision of the necessary means available to ensure that they
do not take place.
Operating readings
Cooling MODE
Suction pressure
Suction temperature (1)
Compressor
Condensation pressure
Condensation temperature (2)
Gas inlet temperature
Liquid outlet temperature (3)
Air
Air inlet temperature
condenser
Outdoor temperature
Air outlet temperature
Air inlet temperature
Air outlet temperature
Air
evaporator
Liquid inlet temperature
Evaporation outlet temperature (4) ºC
Subcooling (2) - (3)
Overheating (4) - (1)
Heating MODE
Suction pressure
Suction temperature (1)
Compressor
Condensation pressure
Condensation temperature (2)
Liquid inlet temperature
Gas outlet temperature (4)
Air
Air inlet temperature
evaporator
Outdoor temperature
Air outlet temperature
Air inlet temperature
Air outlet temperature
Air
condenser
Gas inlet temperature
Liquid outlet temperature (3)
Subcooling (2) - (3)
Overheating (4) - (1)
bar
ºC
bar
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
bar
ºC
bar
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC