Rough-In Dimensions; Foreword - A.O. Smith BTH 120-250(A) Installation & Operating Instructions Manual

Series 970 and 973 commercial gas water heater gas-fired power burner for domestic hot water
Table of Contents

Advertisement

GAS VALVE PIPING
BTH-120
1/2" NPT
BTH-150,
199 & 250
3/4" NPT
Table 1. RECOVERY CAPACITIES - NATURAL GAS / L.P.
Input
Model
BTU/Hr.
BTH - 120
125,000 Nat.
BTH - 120
120,000 L.P.
BTH - 150
150,000 Nat.
BTH - 150
150,000 L.P.
BTH - 199
199,900 Nat.
BTH - 199
185,000 L.P.
BTH - 250
240,000 Nat.
Input
Model
kW
Capacity
BTH - 120
37 Nat.
BTH - 120
35 L.P.
BTH - 150
44 Nat.
BTH - 150
44 L.P.
BTH - 199
58 Nat.
BTH - 199
54 L.P.
BTH - 250
70 Nat.
Recovery capacities are based on heater performance at 94% thermal efficiency.
These designs comply with the latest version of the American National
Standard for Gas Water Heaters, Volume III, ANSI Z21.10.3 / CSA 4.3 M 98
as an automatic circulating tank water heater, and automatic storage water
heaters.
Detailed installation diagrams are found in this manual. These diagrams will
serve to provide the installer with a reference for the materials and methods
of piping necessary. It is highly essential that all water, gas piping and
wiring be installed as shown on the diagrams.
Particular attention should be given to the installation of thermometers at
the locations indicated on the diagrams as these are necessary for checking
the proper functioning of the heater.
CYCLONE XHE BTH 120 - 250 ROUGH-IN-DIMENSIONS
Approx.
Gallon
Capacity
30
40
60
475
356
60
456
342
100
570
427
100
570
427
100
759
569
100
703
527
100
912
684
Approx.
Liter
17°C
22°C
227
1798
1348
227
1726
1295
379
2158
1616
379
2158
1616
379
2873
2154
379
2661
1995
379
3452
2589
TEMPERATURE RISE - DEGREES °F - GALLONS PER HOUR
50
60
70
80
285
237
203
178
274
228
195
171
342
285
244
214
342
285
244
214
456
380
325
285
422
351
301
263
547
456
391
342
TEMPERATURE RISE - DEGREES °C - LITERS PER HOUR
28°C
33°C
39°C
44°C
1079
898
768
674
1037
863
738
647
1295
1079
924
810
1295
1079
924
810
1726
1438
1230
1079
1597
1329
1139
996
2071
1726
1480
1295

FOREWORD

In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local area
where the installation is to be made. These shall be carefully followed in all
cases. Authorities having jurisdiction should be consulted before
installations are made.
In the absence of local codes, the installation must comply with the latest
editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the
National Electric Code, NFPA 70 CAN/CSA 149.1 or .2 and CSA 2C22.1. The
former is available from the CSA International, 8501 East Pleasant Valley
Road, Cleveland, OH 44131, and both documents are available from the
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
2
90
100
110
120
158
142
129
119
152
137
124
114
190
171
155
142
190
171
155
142
253
228
207
190
234
211
192
176
304
274
248
228
50°C
56°C
61°C
67°C
598
538
488
450
575
519
469
432
719
647
587
538
719
647
587
538
958
863
784
719
886
799
727
666
1151
1037
939
863
130
140
110
102
105
98
132
122
132
122
175
163
162
151
210
195
72°C
78°C
416
386
397
371
500
462
500
462
662
617
613
572
795
738