Rough-In Dimensions; Foreword - A.O. Smith CYCLONE XHE BTH 300A Installation & Operating Instructions Manual

Commercial gas water heater gas-fired power burner for domestic hot water
Hide thumbs Also See for CYCLONE XHE BTH 300A:
Table of Contents

Advertisement

GAS VALVE PIPING
BTH-300
3/4" NPT
BTH-400
3/4" NPT
TYPE OF
INPUT
MODEL
GAS
BTUH
300,000
BTH-300
NATURAL
280,000
BTH-300
PROPANE
400,000
NATURAL
BTH-400
400,000
BTH-400
PROPANE
Recovery capacities are based on heater performance at 98% thermal efficiency.
These designs comply with the latest version of the American
National Standard for Gas Water Heaters, Volume III,
ANSI Z21.10.3 / CSA 4.3 as an automatic circulating tank water
heater, and automatic storage water heaters.
Detailed installation diagrams are found in this manual. These
diagrams will serve to provide the installer with a reference for the
materials and methods of piping necessary. It is highly essential
that all water, gas piping and wiring be installed as shown on the
diagrams.
Particular attention should be given to the installation of
thermometers at the locations indicated on the diagrams as these
are necessary for checking the proper functioning of the heater.
ROUGH-IN-DIMENSIONS
TABLE 1, RECOVERY CAPACITIES
U.S. Gallons/Hr and Litres/Hr at TEMPERATURE RISE INDICATED
Approx.
20F°
KW
Capacity
11C°
130 US Gals.
GPH
1782
88
492 Litres
LPH
6745
130 US Gals.
GPH
1663
82
492 Litres
LPH
6295
130 US Gals.
GPH
2376
117
492 Litres
LPH
8993
130 US Gals.
GPH
2376
117
492 Litres
LPH
8993

FOREWORD

30F°
40F°
50F°
60F°
70F°
17C°
22C°
28C°
33C° 39C° 44C° 50C°
1188
891
713
594
509
4496
3372
2698
2248
1927
1109
832
665
554
475
4197
3148
2518
2098
1799
1584
1188
950
792
679
5995
4496
3597
2998
2569
1584
1188
950
792
679
5995
4496
3597
2998
2569
In addition to these instructions, the equipment shall be installed in
accordance with those installation regulations in force in the local
area where the installation is to be made. These shall be carefully
followed in all cases. Authorities having jurisdiction should be
consulted before installations are made.
In the absence of local codes, the installation must comply with the
latest editions of the National Fuel Gas Code, ANSI Z223.1/NFPA
54 and the National Electric Code, NFPA 70 CSA B149.1 and
CSA C22.1. The former is available from the Canadian Standards
Association, 8501 East Pleasant Valley Road, Cleveland, OH 44131,
and both documents are available from the National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269.
2
80F°
90F°
100F° 110°
120F° 130F°
56C° 61C°
67C°
445
396
356
324
297
1686
1499
1349
1226
1124
416
370
333
302
277
1574
1399
1259
1145
1049
594
528
475
432
396
2248
1998
1799
1635
1499
594
528
475
432
396
2248
1998
1799
1635
1499
140F°
72C°
78C°
274
255
1038
964
256
238
968
899
366
339
1384
1285
366
339
1384
1285

Hide quick links:

Advertisement

Table of Contents
loading