Installation Considerations; Rough In Dimensions; Recovery Capacities; Gas And Electrical Characteristics - A.O. Smith BTR 500 Instruction Manual

Series 120/121 commercial gas water heaters
Hide thumbs Also See for BTR 500:
Table of Contents

Advertisement

rough in dimensions

recoVery capacities

gas and electrical characteristics

front View
taBle 1. rough-in-dimensions
Input Rate
Approximate
Btu/hr
Tank Cap
model
kw/hr
G/L
BTR 500
500,000
85
BTR500
147
322
TABLE 2. RECOVERY CAPACITIES, based on 80% efficiency
Input Rate
Approximate
Btu/hr
Tank Cap
model
kw/hr
G/L
BTR 500
500,000
85
BTR 500
147
322
taBle 3. gas and electrical characteristics
model
Gas Type
BTR-500
natural
BTR-500
Propane

installation considerations

top
outlet
1 1/2" npt
Dimensions in Inches/cm
A
B
C
D
E
81.50 17.50 77.25 67.50 27.13 21.00
207
44
196
171
69
30°F
40°F
50°F
17°C
22°C
28°C
1616
1212
970
6118
4588
3671
Gas Supply Pressure
minumum
4.5" W.C. (1.12 kPa)
14" W.C. (3.48 kPa)
11" W.C. (2.74 kPa)
14" W.C. (3.48 kPa)
top
f
inlet
1 1/2" npt
top View
figure 5
Gas
Vent
Inlet
Dia
F
G
h
I
J
1.00
67.50
8.00
27.75
1.50
53
3
171
20
70
1.50
recovery rating Capacities (GPh and LPh) at temperature rise indicated
60°F
70°F
80°F
33°C
39°C
44°C
808
693
606
3059
2622
2294
Gas manifold Pressure
maximum
3.5" W.C. (0.87 kPa)
10" W.C. (2.49 kPa)
8
Back View
Connections
Inlet (nPT)
Outlet (nPT)
Top
Front
Back
Top
Front
Back
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
1.50
90°F
100°F
110°F
120°F
50°C
56°C
61°C
67°C
539
485
441
404
2039
1835
1668
1529
Volts / hz
120/60
120/60
Approx. Ship Weight
Std.
ASme
Lbs/
Lbs/
kgs.
kgs.
812
857
368
389
130°F
140°F
72°C
78°C
373
346
1412
1311
Amperes
<5
<5

Advertisement

Table of Contents
loading

Table of Contents