Empire FAW40SPPXLP-1 Installation Instructions And Owner's Manual page 3

Hide thumbs Also See for FAW40SPPXLP-1:
Table of Contents

Advertisement

Available languages

Available languages

When an existing Category 1 heater is removed or replaced, the
original venting system may no longer be sized to properly vent the
attached appliances. Instructions shall also indicate effects of an
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1.
Seal any unused openings in the venting system.
2.
Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 or the Natural Gas and
Propane Installation Code, CSA B149.1 and these
instructions. Determine that there is no blockage or
restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.
3.
As far as practical, close all building doors and
windows and all doors between the space in which
the appliance(s) connected to the venting system are
located and other spaces of the building.
4.
Close fireplace dampers.
DO NOT OPERATE THIS APPLIANCE WITHOUT FRONT PANELS INSTALLED.
Due to high temperatures the appliance should be located
out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burns or clothing ignition.
Young children should be carefully supervised when they
are in the same room as the appliance.
Clothing or other flammable material should not be placed
on or near the appliance.
Any safety screen or guard removed for servicing an ap-
pliance must be replaced prior to operating the appliance.
Keep burner and control compartment clean.
Installation and repair should be done by a QUALIFIED
SERVICE PERSON. The appliance should be inspected
before use and at least annually by a qualified service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials, etc. It
is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
DO NOT put anything around the furnace that will obstruct
the flow of combustion and ventilation air.
37134-6-0520
INTRODUCTION (CONT'D)
THIS IS A HEATING APPLIANCE
improperly sized venting system (formation of condensate, leakage,
spillage, etc.) and shall specify the following test procedure:
5.
Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they are
operating at maximum speed. Do operate a summer
exhaust fan.
6.
Follow the lighting instructions. Place the appliance
being inspected into operation. Adjust the thermostat
so appliance is operating continuously.
7.
Test for spillage from draft hood equipped appliances
at the draft hood relief opening after 5 minutes of main
burner operation. Use the flame of a match or candle.
8.
If improper venting is observed during any of the
above tests, the venting system must be corrected in
accordance with National Fuel Gas Code, ANSI Z223.1/
NFPA 54 and/or Natural Gas and Propane Installation
Code, CSA B149.1.
9.
After is has been determined that each appliance
connected to the venting system properly vents when
tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-fired
burning appliance to their previous conditions of use.
DO keep the appliance area clear and free from combus-
tible material, gasoline and other flammable vapors and
liquids.
DO examine venting system periodically and replace
damaged parts.
DO make a periodic visual check of pilot and burners.
Clean and replace damaged parts.
CAUTION: Pilot hole cover must be kept tightly closed
during operation.
DO NOT use this heater if any part has been under water.
Immediately call a qualified service technician to inspect
the heater and to replace any part of the control system
and any gas control which has been under water.
This furnace must not be connected to a chimney flue
serving a separate solid-fuel burning appliance.
IMPORTANT: This furnace has a washable permanent
type filter in the door which should be cleaned at least
once per year before the heating season. For dirty or
high use areas more frequent cleaning is required.
Page 3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Faw40ipxlp-1Faw40ipxnat-1Faw40sppxnat-1

Table of Contents