Technical Data; 24 V - Emergency Supply; Pictogram Explanation - D+H RZN 4402-KS V2 Original Instructions Manual

Hide thumbs Also See for RZN 4402-KS V2:
Table of Contents

Advertisement

Available languages

Available languages

Technical data

Type
Power supply
Rated power
Stand-by operating
Output voltage
Ripple
Output rated current
Number of lines / groups * 1 / 1
Fire detector per line
SHEV button per line
Current per group **
Mode of operation
- Monitoring
- Alarm / Ventilation
Housing
Colour
Ingress protection
Protection class
Temperature range
Dimensions WxHxD
* D+H Highspeed (HS) drives will be supported.
** The total current of the control panel must not be exceeded.

24 V - Emergency supply

Emergency power supply for 72 hours.
Use VdS approved storage batteries only!
RZN 4402-K(S) V2: 2x 12V / 1,2 Ah ±0,2Ah (Type 1)
RZN 4404-K(S) V2: 2x 12V / 2,2 Ah ±0,3Ah (Type 2)
With connection of D+H alarm devices:
RZN 4402-K(S) V2: 2x 12V / 2,2 Ah ±0,3 Ah (Type 2)
RZN 4404-K(S) V2: 2x 12V / 3,4 Ah ±0,3 Ah (Type 8)
(* Only with -KS version possible!)
99.823.80 3.1/09/13
RZN 4402-K (-KS)
230 V AC, 50 Hz
60 VA
5,6 W
24 V DC
2 Vss, load-dependent
2 A
max. 14 pcs.
max. 8 pcs.
max. 2 A
Continuous duty
Short-time duty (30 % DC)
Plastic with steel sheet door (steel sheet)
white (light grey)
IP 30 (IP 54)
II, with fuctional ground (I)
-5 ... +40 °C
310 x 310 x 100 mm (400 x 300 x 120 mm)
English
RZN 4404-K (-KS)
230 V AC, 50 Hz
120 VA
5,8 W
4 A
1 / 1
max. 14 pcs.
max. 8pcs.
max. 4 A

Pictogram explanation

SHEV alarm
Malfunction
Control panel O.K.
OK
D+H window drive
Mains existing
Vent button function "OPEN"
Smoke-/ vent button function "CLOSE"
Charging voltage regulator
Ground short
20
40
OPEN running time limitation
sec
2
60
15
30
ventilation time limitation
min
2
45
RZN 4402-K / RZN 4404-K
21/36

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzn 4404-k v2Rzn 4402-k v2Rzn 4404-ks v2