Toshiba RAV-GV1601ATP-TR Service Manual page 108

Table of Contents

Advertisement

WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant
gas leaking out, its concentration will not exceed a set limit.
The refrigerant R32 which is used in the air conditioner is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains
more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from
leakage of R32 is almost non-existent.
If a conditioner system is to be installed in a small room, select a suitable model and installation procedure so
that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an
emergency, measures can be made before injury can occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak detection device.
The concentration is as given below.
≤ Concentration limit (kg/m
3
Total amount of refrigerant (kg)
)
Min. volume of the indoor unit installed room (m3)
Refrigerant concentration limit shall be in accordance with local regulations.
- 108 -

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gv1601atp-e

Table of Contents