INSTRUCTION MANUAL
DeviceNet INTERFACE MODULE
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ........................................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ UNPLUGGING THE MODULE
Before you remove the module from its base or mount it,
turn off the power supply for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive
remedies, under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: info@m-system.co.jp
MODEL
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base Model: R3-BSx, or Model: R3-
BSWx for free I/O address capability.
Before mounting the Network Interface Module R3-GD1
onto the base, be sure to configure the module as explained
below.
■ DATA ALLOCATION
Use the side DIP SW1 to set the number of slots which the
module is assigned to.
See "TRANSMISSION DATA DESCRIPTIONS."
■ NODE ADDRESS & TRANSFER RATE
See "COMPONENT IDENTIFICATION."
■ NETWORK SLOTS ON THE BASE
I/O 1
I/O 2
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module(s) and Power Module are mounted basi-
cally at the right end though technically they could be
mounted in any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
It is available to assign the module to max. 8 slots. The as-
signed slots numbers can not be used again for the real I/O
modules which need to be mounted on the same base. Don't
set the interface module for more than 16 slots as it can not
read the data for more than 16 modules.
R3-GD1
R3-GD1
I/O n
EM-8465
P.  / 4

Advertisement

loading

Summary of Contents for M-system R3-GD1

  • Page 1 M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
  • Page 2 R3-GD1 COMPONENT IDENTIFICATION � FRONT VIEW � SIDE VIEW Functions MS LED Transfer Rate NS LED Node Address Configuration Jack Terminal Block Module Allocation ■ INDICATORS ■ FRONT DIP SW The following table defines the LED states of the MS, and •...
  • Page 3 R3-GD1 TERMINAL CONNECTIONS Connect the unit as in the diagram below. ■ DIMENSIONS mm (inch) 27.5 (1.08) 109 (4.29) POSITIONING GUIDE 6–M3 SCREW TERMINAL COVER ■ CONNECTION DIAGRAM INTERNAL COMM. BUS CAN_H To Other Drain DeviceNet Devices CAN_L V –...
  • Page 4 1 module is equivalent to 1 I/O module with 16 words analog input and 16 words analog output. Max. 4 modules (64 words input, 64 words output) transmission is available. R3-GD1 seems as if max. 4 I/O modules are mounted to 4 slots via Device- Net.