Mitsubishi KXZ Series Technical Manual page 236

Vrf inverter multi-system air-conditioners
Hide thumbs Also See for KXZ Series:
Table of Contents

Advertisement

Remote
7-segment
control
display
error code
E48
E48
E49
E49
E53
E53
E54
E54
E56
E56
E58
E58
E59
E59
E63
E63
2) Option control in-use
SL1N-E
Indoor unit
SL2NA-E
control PCB
SL4-AE/BE
Error
Red
Red
code
LED
LED
Keeps
Stays
E75
flashing
OFF
3) Operation code
7-segment
display
[oP7]
Model setting error due to DIP switch
Extremely low outside temperature operation
[oP8]
stopped when outdoor temperature <-22°C
Name of inspection
Outdoor DC fan motor anomaly
Low pressure error
Suction pipe temperature sensor anomaly (Tho-S)
High pressure sensor anomaly (PSH)/Low pressure sensor
anomaly (PSL)
Power transitor temperature sensor anomaly (Tho-P1)
Anomalous compressor by loss of synchronism
Compressor startup failure
Emergency stop
Outdoor unit
control PCB
Location of
Green
Red
Green
LED
LED
LED
SL1N-E
Keeps
Stays
Keep
SL2NA-E
flashing
OFF
flashing
SL4-AE/BE
Reason for display
-
Description of trouble
trouble
・Communication enor (Deflective comm-
unication circuit on the main unit of
SL1N-E, SL2NA-E or SL4-AE/BE)
Unit status
Normal operation impossible Check the settings of SW3-2 and
Normal operation impossible
219
-
'20 • KX-T-373
Classification
Page
DC fan motor error
262
System error
263
Sensor wire breakage
264
Sensor wire breakage
265
Sensor wire breakage
266
System error
267
System error
268
Site setting error
269
Repair
method
Replacement
How to deal
SW4-1 to 4-4. See page 215.
Use this machine in an
environment where the outdoor
temperature is> -20°C.

Advertisement

Table of Contents
loading

Table of Contents