Mitsubishi KXZ Series Technical Manual page 46

Vrf inverter multi-system air-conditioners
Hide thumbs Also See for KXZ Series:
Table of Contents

Advertisement

Model RC-E5
Exposed mounting
48
0.3mm
×2 cores
2
In case of pulling out
from upper left
L C D
TEMP
Exterior appearance
(Munsell color)
Embedded mounting
Wall surface
19
Wiring specifications
(1) If the prolongation is over 100m, change to the size below.
But, wiring in the remote control case should be under 0.5mm
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
100 to 200m
In case of pulling out
from center
ON/OFF
X, Y Terminal block
Attach M3 screw
with washer
120
Pearl white
(N8.5) near equivalent
Remote
control
outline
Wiring
Wiring outlet
Electrical box
12×7 slot hole
Not included
1 Installation screw for remote control
Length
Wiring thickness
0.5mm
Under 300m
0.75mm
Under 400m
1.25mm
Under 600m
2.0mm
Wiring outlet
Cut off the upper thin part of remote control lower case with a nipper or knife,
and grind burrs with a file etc.
In case of pulling out
from upper left
Upper
Board
X
Y
Lower
Wiring
In case of pulling out from
upper left
The peeling-off length of sheath
Pulling out from upper left
Pulling out from center
X wiring : 215mm
X wiring : 170mm
Y wiring : 195mm
Y wiring : 190mm
Remote control installation dimensions
120
46
23
44
11.5
11
Installation hole
9.5×5 slot hole 4 places
M4 screw (2 pieces)
. Change the wire size outside of
2
× 2 cores
2
× 2 cores
2
× 2 cores
2
× 2 cores
2
43
-
-
'20 • KX-T-373
In case of pulling out
from center
Upper part
Lower case
Lower part
Sheath
Upper
Upper cace
Board
X
Y
Lower
In case of pulling out from center
The peeling-off length
Tighten the screws after
cutting off the thin part of
screw mounting part.
Unit:mm
PJZ000Z295
Sheath
Upper cace
Wiring
of sheath

Advertisement

Table of Contents
loading