Installation
Ventilation
DIRECT FLUE ARRANGEMENT
When the installation of a mechanically driven exhaust
hood is impractical the oven may be vented by a direct
flue arrangement.
WARNING!!
It is essential that the direct flue be installed
as follows. Incorrect installation will result in
unsatisfactory baking and oven damage.
The flue must be class B or better. The height of the flue
should rise 6-8 ft (2-2.5 m) above the roof of the build-
ing or any proximate structure. Never direct vent the oven
into a hood. The flue should be capped with a UL Listed
type vent cap to isolate the unit from external environ-
mental conditions.
The direct vent cannot replace air consumed and vented
by the oven. Provisions must be made to supply the room
with sufficient make-up air. Total make-up air require-
ments for each oven section should be approximately 30
CFM (.85 m3) per section. To increase the supply air en-
tering the room, a ventilation expert should be consulted.
FLUE DIAMETER
Oven
DFG-100-K12-ES
DFG-200-K12-ES
Single
Double
6" (15cm)
6" (15cm)
6" (15cm)
6" (15cm)
Installing the draft hood
Ovens ordered for direct venting are supplied with a draft
hood. Install the draft hood as follows:
1. Install draft diverter using the screws provided as
shown below.
2. Place the draft hood over the draft diverter.
3. Secure both ends with the sheet metal screws pro-
vided.
Draft diverter
Drafthood
Two screws
in back
One screw
into frame
8
Flue
One screw
Front of
Oven
Figure 7