Holiday Programs; Heating Circuits - Potterton Eurocondense five 400 kW Installation Manual

Gas condensing boiler
Table of Contents

Advertisement

7713465 - 05 - 23102019
Heating phases (501 — 606)
Up to 3 heating phases can be set per heating circuit. These are active on
the days selected under Preselection (prog.no. 500, 520, 540, 560, 600).
During the heating phases the system heats to the set comfort setpoint.
Outside the heating phases, the system heats to the reduced setpoint.
Important
The time programs are only activated in Automatically operating
mode.
Copy? (515–615)
The time program for one day can be copied and assigned to another or
several other days.
Important
Day blocks cannot be copied.
Default values (516–616)
Setting of the default values given in the setting table
9.2.5

Holiday programs

Preselection (641 - 661)
Important
The heating circuits may be set to a selectable operation level with
the holiday programme during a certain holiday period.
8 holiday periods can be selected with this preselection.
Start of holiday (642 - 662)
Entering the holiday start.
End of holiday (643 - 663)
Entering the holiday end.
Operating level (648-668)
Selection of the operating level (Reduced or Protection) for the holiday
programme
Important
A holiday period always ends on the last day at 12:00 AM (23:59).
The holiday programmes are only activated in the operation mode
Automatically.
See
See also the User manual EC five.
9.2.6

Heating circuits

Operating mode (700, 1000, 1300)
The operating mode can be set via the operation mode button at the boiler
or at the room device. For other service tools, the operating mode is set
via this control line.
Protection: The heating is switched off in protection mode. The room
remains protected against frost however (Frost protection setpoint, e.g.
prog. no. 714).
Automatic: In automatic mode, the room temperature is controlled in
accordance with the time program that is selected.
Reduced: In reduced operation mode the room temperature is kept
constantly to the set Reduced setpoint(e.g. prog. no. 712).
Comfort: In comfort mode the room temperature is kept constantly to the
set Comfort setpoint(e.g. prog. no. 710). Eco functions are not activated.
9 Settings
93

Advertisement

Table of Contents
loading

Table of Contents