Electrical Wiring; Electrical Requirement - Fujitsu AIRSTAGE ARUL4TLAV1 Installation Manual

Hide thumbs Also See for AIRSTAGE ARUL4TLAV1:
Table of Contents

Advertisement

Press fi rmly
Press fi rmly
Slit
Press fi rmly
STEP 2
• FINISH
Check that there is no gap
between the unit and the drain
hose insulation.
Note:
Check for drainage
Pour about 1 liter of water from the position shown
in the diagram or from the airflow outlet to the dew
tray. Check for any abnormalities such as strange
noises and whether the drain pump functions
normally.
CAUTION
Make sure the drain water is properly drained.

6. ELECTRICAL WIRING

Electrical work must be performed in accordance with this Manual by a person certified
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the all units.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as overheat-
ing the terminals, electric shock, or fire.
Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as electric
shock or fire through exposure to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or fire.
Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can
cause electric shock or fire.
Match the terminal block numbers and connection cable colors with those of the outdoor
unit . Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fire.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric discharge may occur.)
We suggest installing GFEB breakers or follow local electrical code. When installing
this system, install using ground fault equipment breakers (GFEB) to reduce the risk of
leaking current which result in electric shock or potential fire.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable firmly to the terminal board. Imperfect installation may
cause a fire.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
Slit
Press fi rmly
Press fi rmly
Roll the in-
sulation over
the joint.
STEP 3
Do not cover the
panel window.
WARNING
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 2 in (50 mm) or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of the
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor unit for more than 10 seconds to discharge static elec-
tricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.

6.1. Electrical requirement

• Select the power cable type and size
in accordance with relevant local and
national regulations.
• Specifications for local wiring power cord and branch wiring are in compliance with local
code
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Breaker should be installed at every refrigerant system. Do not use a breaker in a different
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
MAX. CKT. BKR
Model
MCA
(Fuse capacity)
ARUL4TLAV1
0.35 A
15 A
When the power crossover wiring is done, make it so that the total of the MCA of the con-
nected RB units and indoor units does not exceed the 11 A. For RB unit MCA, refer to the
RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Maximum connect-
able "indoor units"
Breaker capacity
or "indoor units +
RB units" (*1)
30 mA, 0.1 sec or less
36 or less
100 mA, 0.1 sec or less
37 to 121 (*2)
6.1.1. Cable specifi cations
Cable size
Use
(AWG)
Power supply
16 to 10
Sheathed PVC cable
cable
LEVEL 4 (NEMA) non-
Transmission
polar 2core, twisted
22
cable
pair solid core diameter
0.026 in (0.65mm)
22 to 16
Sheathed PVC cable
Remote con-
troller cable
Thermostat cable 2
(2-wire type)
18
core
Remote con-
troller cable
22
Sheathed PVC cable
(3-wire type)
CAUTION
Voltage rating
208/230 V
Operating range
187 to 253 V
• MCA: Minimum Circuit Ampacity
• MAX. CKT. BKR : Maximum Circuit
Breaker
*1: Heat pump type: indoor units,
Heat recovery type: indoor units
and RB units.
*2: If the 100 mA capacity breaker is
not provided, split the quantity of
the indoor units into small groups
of 9 units or less and provide a
breaker with capacity of 30 mA for
each group.
Cable type
Remarks
2 cable + earth (ground)
LONWORKS ® compatible
cable
Non-polar 2 core, twisted
pair
Use sheathed non twisted
pair cable
Polar 3 core
En-8