6. ELECTRICAL WIRING

Cable
Cable size [mm²]
Power Supply Cable
6
Connection Cable
1.5
Limit the voltage drop less than 2 %. Increase the cable diameter if voltage drop is 2 % or
more.

6.1. Selecting circuit breaker and wiring

Be sure to install a breaker of the specifi ed capacity.
Regulation of cables and breaker diff ers from each locality, refer in accordance with
local rules.
Breaker and wiring specifi cations
Breaker
Earth leakage
Power supply cable*
capacity
breaker
[A]
[mA]
30
30
* Limit the voltage drop less than 2 %. Increase the cable diameter if voltage drop is 2 %
or more.
• Selected sample: Select the correct cable type and size according to the country or
region's regulations.
• Select the appropriate breaker of the described specifi cation according to the national
or regional standards.
• Select the breaker that enough load current can pass through it.
• Before starting work check that power is not being supplied to all poles of the indoor
unit and outdoor unit.
• Install the disconnect device with a contact gap of at least 3mm in all poles nearby
the units. (Both indoor unit and outdoor unit)

6.2. Notes for electrical wiring

Wiring connections must be performed by a qualified person in accordance with speci-
fications.
The rated supply of this product is 50 Hz, 400 V of 3-phase, 4-wire. Use a voltage within
the range of 342 to 456 V (50 Hz).
Make sure to perform earthing (grounding) work. Improper earthing (grounding) work
can cause electric shocks.
Before connecting the cables, make sure the power supply is Off.
Be sure to install an earth (ground) leakage breaker. Otherwise, it will cause electric
shock or fire.
Select a breaker (Included with earth leakage circuit breaker) of appropriate capacity
and install one at every power supply of an outdoor unit. Wrong selection of breakers or
transition wiring will lead to electric shock and fire.
Do not connect AC power supply to the transmission line terminal board.
Improper wiring can damage the entire system.
Install a breaker (Included with earth leakage circuit breaker) in accordance with the
related laws and regulations.
Connect the connector cable securely to the terminal.
Faulty installation can cause a fire.
Make sure to secure the insulation portion of the connector cable with the cable clamp.
A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the power
factor, the condenser may overheat.
Before servicing the unit, turn the power supply switch Off. Then, do not touch electric
parts for 10 minutes due to the risk of electric shock.
Always use a separate power supply line protected by a circuit breaker operating on all
cables with a distance between contact of 3 mm for this unit.
Do not modify power cable, use extension cable or branch wiring. Improper use may
cause electric shock or fire by poor connection, insufficient insulation or over current.
Use ring terminals and tighten the terminal screws to the specified torques, otherwise,
abnormal overheating may be produced and possibly cause serious damage inside the
unit.
Securely install the electrical box cover on the unit. An improperly installed service
panel can cause serious accidents such as electric shock or fire through exposure to
dust or water.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
Type
Remarks
4 Cable + Ground
Type60245 IEC66
3 Φ 400 V
3 Cable + Ground
Type60245 IEC57
1 Φ 230 V
CAUTION
Connection cable*
Cable size
Cable size
[mm²]
[mm²]
6
1.5
WARNING
The primary power supply capacity is for the air conditioner itself, and does not include
the concurrent use of other devices.
Connect the power cables in positive phase sequence. If there is a missing phase con-
nection, the unit will not operate normally.
Do not use crossover power supply wiring for the outdoor unit.
If the electrical power is inadequate, contact your electric power company.
Install a breaker (Included with earth leakage circuit breaker) in a location that is not
exposed to high temperatures.
If the temperature surrounding the breaker is too high, the amperage at which the
breaker cuts out may decrease.
Use a breaker (Included with earth leakage circuit breaker) that is capable of handling
high frequencies. Because the outdoor unit is inverter controlled, a high-frequency earth
leakage circuit breaker is necessary to prevent a malfunction of the breaker itself.
When the electrical switchboard is installed outdoors, place it under lock and key so that
it is not easily accessible.
Never bundle the power supply cable and connection cable, remote control cable
together. Separate these cable by 50 mm or more. Bundling these cables together will
cause miss operation or breakdown.
Always keep to the maximum length of the connection cable. Exceeding the maximum
length may lead to erroneous operation.
The static electricity that is charged to the human body can damage the control PC
board when handling the control PC board for address setting, etc.
Please keep caution to the following points.
Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker).
Touch the metal section (such as the unpainted control box section) of the indoor or
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.
Never touch the component terminal or pattern on the PC board.
How to connect wiring to the terminal
Caution when wiring cable
• When stripping off the coating of a lead wire, always use a special tool such as a wire
stripper. If there is no special tool available, carefully strip the coating with a knife etc.
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect
to the terminal block.
(2) Securely clamp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
Strip : 10 mm
(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
Screw with special washer
Ring terminal
Wire
Terminal blocks
(6) See the table below for the terminal screw tightening torques.
Tightening torque [N·m (kgf·cm)]
M4 screw
M5 screw
CAUTION
Ring terminal
Sleeve
Screw with
special washer
Ring terminal
Wire
1.2 to 1.8 (12 to 18)
2.0 to 3.0 (20 to 30)