Troubleshooting
Problem
The display shows
"Not enough UV. Add!"
The display shows
"Not enough oil. Add!"
The display shows
"Max. filling time
exceeded! Carry on?
The display shows
"External tank empty or
closed valve. Check!
The display shows
"Change the equipment
"
drier filter! Go on?
The display shows
"Change the vacuum pump
"
oil! Go on?
The display shows
"Printer not in line!
"
Carry on?
The display shows
"
Error 01"
116
Cause
This message appears dur-
ing the filling process if there
is not enough UV additive in
the container to finish the
process.
Message that appears during
the filling process if there is
not enough fresh oil in the
container to finish the pro-
cess.
Message that appears during
the filling process if the set
amount of refrigerant cannot
"
be filled.
Message that appears at the
start or during the filling of
the internal refrigerant con-
"
tainer if the set refrigerant
quantity cannot be attained.
This message appears when
you switch on the
AirConServiceCenter.
This message appears when
you switch on the
AirConServiceCenter.
Message indicates a printer
fault.
It was not possible to reduce
the pressure sufficiently
before the pressure increase
test.
AirConServiceCenter
Remedy
Fill the UV additive container.
Top up the fresh oil container
with a suitable oil type.
Check that
AirConServiceCenter
connections are not blocked.
Check if the external refriger-
ant container still contains
enough refrigerant or if the
valves of the external refrig-
erant container are open.
Change the internal filter as
soon as possible (chapter
"Changing the dryer filter" on
page 104). To skip this, press
ENTER for 3 seconds.
Change the vacuum pump oil
as soon as possible (chapter
"Changing the vacuum pump
oil" on page 108). To skip
this, press ENTER for
3 seconds.
Check if there is paper in the
printer.
Check if the printer is
switched on (yellow LED
must light up constantly).
Check that the cover is
closed properly.
Check air conditioner and
connections for leaks, con-
strictions and ice build-up.
Check pressure transducer
calibration.