Initiating Zcvpsof Automatically And Setting Mode To Impedance; Initiating Zcvpsof Automatically And Setting Mode To Uilevel; Completing The Test; Current Protection - ABB Relion 650 Series Commissioning Manual

Line differential protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 395-UEN C
1.
Set
2.
Activate the switch onto fault BC input.
During normal operating conditions, the BC input is de-energized.
3.
Apply a three-phase fault condition corresponding to a fault at approximately 45% of the
line or with impedance at 50% of the used zone setting and current greater than 30% of
IBase .
The ZACC input is activated.
4.
Check that the TRIP output, external signals and indication are obtained.
9.4.3.2

Initiating ZCVPSOF automatically and setting mode to impedance

1.
Set
2.
Deactivate the switch onto fault BC input.
3.
Set the current and voltage inputs to lower than
4.
Apply a three-phase fault condition corresponding to a fault at approximately 45% of the
line or with impedance at 50% of the used zone setting and current greater than 30% of
IBase .Apply a two-phase fault condition corresponding to a fault at approximately 45%
of the line or with impedance at 50% of the used zone setting and current greater than
30% of
The ZACC input is activated.
5.
Check that the correct TRIP output, external signals and indication are obtained.
9.4.3.3

Initiating ZCVPSOF automatically and setting mode to UILevel

1.
Set
2.
Deactivate the switch onto fault BC input.
3.
Set the current and voltage inputs to lower than
4.
Apply the three-phase currents in such a way that the magnitudes are greater than
and the three-phase voltages in such a way that the magnitudes and lower than
least for the duration of the
5.
Check that the correct TRIP output, external signals and indication are obtained.
9.4.3.4

Completing the test

continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
9.5

Current protection

9.5.1
Instantaneous phase overcurrent protection 3-phase output
PHPIOC
Prepare the IED for verification of settings outlined in Section
settings".
Values of the logical signals for PHPIOC are available on the local HMI under Main menu/
Tests/Function status/Current protection/InstPhaseOverCurrent(50,3I>>)/
PHPIOC(50;3I>>):x, where x = 1, 2, and 3.
The Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
Line differential protection RED650
Commissioning manual
AutoInitMode to DLD disabled and Mode to Impedance .
AutoInitMode to Voltage and Mode to Impedance .
IBase .
AutoInitMode to Voltage and Mode to UILevel .
© Copyright 2017 ABB. All rights reserved
IPh< and UPh< for at least one second.
IPh< and UPh< for at least one second.
tDuration setting.
Testing functionality by secondary injection
GUID-E83E1B3D-026C-48DB-BB9B-43C6597DE5DB v5
TESTMODE setting to Off .
"Preparing the IED to verify
Section 9
M13850-27 v8
IPh<
UPh< at
M13850-41 v5
SEMOD53531-1 v1
M11754-3 v8
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red650