• Constant current constant voltage charging (CCCV) is recommended for LFP batteries. Refer to diagram
below for illustration:
4.4. Discharging
• Do not exceed the maximum discharge current as specified in the data sheet.
• Avoid discharging the LFP battery at its maximum current (1C) several times in succession, as this may
cause the BMS to cut out.
• For 100Ah LFP battery, the maximum continuous load should not exceed 1100W. A maximum 1000W
inverter can be connected to avoid damaging the battery including the BMS and the cells. Likewise, for
200Ah LFP battery, an inverter not exceeding 2000W is recommended.
• If connecting two 100Ah LFP batteries in parallel, a maximum 2000W inverter can also be recommended.
Continuous discharge at maximum current at high temperature will result in reduced run time and potentially BMS cut-off for temperature protection.