8 Configuration
#
Code
[A.6.3.2]
[4-09]
Type:
▪ 0 (Current): The limitation values are
set in A.
▪ 1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3]
[5-05]
Value: Only applicable in case of full
time power limitation mode.
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.4]
[5-09]
Value: Only applicable in case of full
time power limitation mode.
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1]
[5-05]
Limit DI1
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.5.2]
[5-06]
Limit DI2
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.5.3]
[5-07]
Limit DI3
0 A~50 A, step: 1 A (default: 50 A)
[A.6.3.5.4]
[5-08]
Limit DI4
0 A~50 A, step: 1 A (default: 50 A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1]
[5-09]
Limit DI1
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.2]
[5-0A]
Limit DI2
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.3]
[5-0B]
Limit DI3
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
[A.6.3.6.4]
[5-0C]
Limit DI4
0 kW~20 kW, step: 0.5 kW (default:
20 kW)
Priority: Only applicable in case of an optional EKHW.
Installer reference guide
70
Description
#
Code
[A.6.3.7]
[4-01]
Power consumption control
DISABLED [4‑08]=0
▪ 0 (None)(default): Backup heater and
booster
simultaneously.
▪ 1 (BSH): The booster heater is
prioritized.
▪ 2 (BUH): The backup heater is
prioritized.
Power consumption control
ENABLED [4‑08]=1 or 2
▪ 0 (None)(default): Depending on the
power limitation level, the booster
heater will be limited first, before the
backup heater is limited.
▪ 1 (BSH): Depending on the power
limitation level, the backup heater will
be limited first, before the booster
heater is limited.
▪ 2 (BUH): Depending on the power
limitation level, the booster heater
will be limited first, before the backup
heater is limited.
Note: In case of power consumption control is DISABLED (for all
models) the setting [4‑01] defines whether backup heater and
booster heater can operate simultaneously, or if the booster heater/
backup heater has priority over the backup heater/booster heater.
In case of power consumption control is ENABLED (only for EHBH/
X04+08 and EHVH/X04+08), the setting [4‑01] defines the priority of
the electrical heaters depending on applicable limitation.
Average timer
The average timer corrects the influence of ambient temperature
variations. The weather-dependent set point calculation is done on
the average outdoor temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
[A.6.4]
[1-0A]
Outdoor average timer:
▪ 0: No averaging (default)
▪ 1: 12 hours
▪ 2: 24 hours
▪ 3: 48 hours
▪ 4: 72 hours
INFORMATION
If the power saving function is activated (see [E‑08]), the
average outdoor temperature calculation is only possible in
case the external outdoor temperature sensor is used. See
"5.7  Setting up an external temperature sensor"  on
page 22.
Offset temperature external outdoor ambient sensor
Only applicable in case of an external outdoor ambient sensor is
installed and configured.
You can calibrate the external outdoor ambient temperature sensor.
It is possible to give an offset to the thermistor value. The setting can
be used to compensate for situations where the external outdoor
ambient sensor cannot be installed on the ideal installation location
(see installation).
#
Code
[A.6.5]
[2‑0B]
–5°C~5°C, step: 0.5°C (default: 0°C)
ERLQ004~008CA + EHVH/X04+08S18+26CB
Description
heater
can
operate
Description
Description
Daikin Altherma – Low temperature split
4P384973-1D – 2018.07