Sanyo SAP-K181GJH Technical & Service Manual page 44

Indoor/outdoor units
Table of Contents

Advertisement

9-3-4. Only outdoor fan does not run.
• Check fan rotation.
Turn fan gently once or twice by
hand.
• Measure resistance of indoor fan
motor winding.
• Check fan motor capacitor.
9-3-5. Only compressor does not run.
• Measure coil resistance of
starting relay.
• Measure resistance of
compressor motor winding.
• Measure coil resistance of
power relay.
Fan cannot
be turned.
OK
• Check capacitors.
(SR)
• Either internal protector or
overload relay is working.
• Temperature of compressor
is abnormally high.
Refrigerant gas shortage.
(PR)
Rotor may be locked up.
• Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
(Either C or BC)
YES
(49C or OLR)
YES
YES
YES
NO
41
Remove foreign
matter or repair.
Repair or replace.
Charge refrigerant gas (R22).

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sap-k241gjhSap-c181ghSap-c241gh

Table of Contents