5-3. Cooling Capacity
Indoor Unit
SAP – K181GJH
Outdoor Unit
SAP – C181GH
240V Single Phase 50Hz
RATING CAPACITY
AIR FLOW RATE
EVAPORATOR
ENT. TEMP. °C
W.B.
D.B.
15
17
19
21
23
TC :
Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
5.05 kW
760 m
CONDENSER
OUTDOOR AMBIENT TEMP. °C
30
TC
4.65
CM
1.81
21
SHC
3.09
23
SHC
3.44
25
SHC
3.80
27
SHC
4.15
29
SHC
4.51
31
SHC
4.65
TC
4.98
CM
1.86
21
SHC
2.72
23
SHC
3.08
25
SHC
3.43
27
SHC
3.79
29
SHC
4.14
31
SHC
4.50
TC
5.30
CM
1.92
21
SHC
2.34
23
SHC
2.69
25
SHC
3.05
27
SHC
3.40
29
SHC
3.76
31
SHC
4.11
TC
5.62
CM
1.97
23
SHC
2.30
25
SHC
2.66
27
SHC
3.01
29
SHC
3.37
31
SHC
3.72
TC
5.95
CM
2.02
25
SHC
2.24
27
SHC
2.59
29
SHC
2.95
31
SHC
3.30
3
/h
35
40
43
4.42
4.16
3.83
1.94
2.13
2.37
2.97
2.83
2.66
3.32
3.18
3.02
3.68
3.54
3.37
4.03
3.89
3.73
4.39
4.16
3.83
4.42
4.16
3.83
4.75
4.46
4.11
2.00
2.18
2.43
2.61
2.47
2.30
2.96
2.82
2.65
3.32
3.18
3.01
3.67
3.53
3.36
4.03
3.89
3.72
4.38
4.24
4.07
# 5.05
4.75
4.37
2.06
2.25
2.50
2.22
2.08
1.92
2.58
2.44
2.27
2.93
2.79
2.63
3.29
3.15
2.98
3.64
3.50
3.34
4.00
3.86
3.69
5.35
5.03
4.63
2.12
2.31
2.57
2.19
2.05
1.88
2.54
2.40
2.24
2.90
2.76
2.59
3.25
3.11
2.95
3.60
3.47
3.30
5.62
5.26
4.89
2.17
2.37
2.63
2.10
1.97
1.83
2.46
2.32
2.18
2.81
2.67
2.54
3.17
3.03
2.89
16