6. Electrical Wiring

6.1 General Check

CAUTION
·When clamping the wiring, use the included clamping material to prevent outside pressure being
exerted on the wiring connections and clamp firmly.
When doing the wiring, make sure the wiring is neat and does not cause the control box lid to stick up, then
·
close the cover firmly. When attaching the control lid, make sure you do not pinch any wires.
Outside the machine, separate the weak wiring(remote controller and transmission wiring) and strong
·
wiring(earth and power supply wiring) at least 50 mm so that they do not pass through the same place
together. Proximity may cause electrical interference, malfunction, and breakage.
WARNING
If the fuse blows, please call the service agency to replace it. Please do not replace it by yourself, or else
it may result in accident, for example, shock.
(1) As shown in Fig. 6.1, remove the screws on the control box.
(2) Connect the power cord and earth wire to the main terminal.
(3) The remote control wire to the subsidiary terminal box.
(4) Connect the power supply of the indoor and outdoor units to the main terminal.
(5) Tie the wire in the control box with the clamp tightly.
(6) After finishing the wiring, seal the wiring hole with the sealing material (with the lid)
to prevent the condensed water and insects entering.

6.2 Electrical Wiring Diagram

Outdoor unit
Terminal
1(L)
2(N)
4(SI)
L
N
Power supply
18/25/30/36/42K(RAS-B42TFTSNAA)
Air outlet
Fig.6.1
Remove the screws on the control box
Indoor unit
Terminal
1(L)
Transmission Cable
2(N)
4(SI)
The lid of the control box
Power supply
27
Installation and Maintenance
Air inlet
Outdoor unit
Terminal
1(L)
Transmission Cable
2(N)
4(SI)
W
V
U
N
Three-phase series
42(RAS-B42TFTSMAA)/48/55K
Indoor unit
Terminal
1(L)
2(N)
4(SI)