Safety Guidelines for Hazardous Locations

The NI-9426 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous
locations; Class I, Zone 2, AEx nA IIC T4 Gc and Ex nA IIC T4 Gc hazardous locations;
and nonhazardous locations only. Follow these guidelines if you are installing the
NI-9426 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
been switched off or the area is known to be nonhazardous.
Caution
the area is known to be nonhazardous.
Caution
Division 2, or Zone 2.
Caution
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use in Europe and
Internationally
The NI-9426 has been evaluated as Ex nA IIC T4 Gc equipment under
DEMKO 07ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI-9426 is marked
II 3G and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9426 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that has been
evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
6
ni.com
Do not disconnect I/O-side wires or connectors unless power has
Do not remove modules unless power has been switched off or
Substitution of components may impair suitability for Class I,
The system must be installed in an enclosure certified for the
NI-9426 Getting Started