Diagnostic Messages - Siemens SIMATIC ET 200SP Manual

Digital input module f-di 8x24vdc hf (6es7136-6ba00-0ca0)
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

6.3

Diagnostic messages

Diagnostic messages
Module faults are indicated as diagnostics (module status).
Once the fault is eliminated, the F-module must be reintegrated in the safety program. For
additional information on passivation and reintegration of F-I/O, refer to the SIMATIC Safety
– Configuring and Programming
(http://support.automation.siemens.com/WW/view/en/54110126) manual.
Table 6- 6
Diagnostic messages of the F-DI 8×24VDC HF
Diagnostic message
Overtemperature
Parameter assignment error
Load voltage missing
Access to retentive storage of
F-address not possible
Different destination address
(F_Dest_Add)
Invalid destination address
(F_Dest_Add)
Invalid source address
(F_Source_Add)
Watchdog time is 0 ms
(F_WD_Time or
F_WD_Time2)
"F_SIL" parameter exceeds
the application-specific SIL
"F_CRC_Length" parameter
does not match the
generated CRC
Digital input module F-DI 8x24VDC HF (6ES7136-6BA00-0CA0)
Manual, 07/2013, A5E03858068-01
Fault
code
5
An excessively high temperature was
D
measured in the F-module.
16
Parameter assignment errors include:
D
The F-module cannot use the
parameters (unknown, invalid
combination, etc.).
The F-module parameters have not
been configured.
17
Missing or insufficient supply voltage L+
D
30
The F-destination address stored in the
D
coding element cannot be accessed.
64
The PROFIsafe driver has detected a
D
different F-destination address.
65
The PROFIsafe driver has detected an
D
invalid F-destination address.
66
The PROFIsafe driver has detected an
D
invalid F-source address.
67
The PROFIsafe driver has detected an
D
invalid watchdog time.
68
The PROFIsafe driver has detected a
D
discrepancy between the SIL setting of
the communication and the application.
69
The PROFIsafe driver has detected a
D
discrepancy in the CRC length.
Meaning
Interrupts/diagnostic messages
6.3 Diagnostic messages
Remedy
Operate the F-module within the
specified temperature range. (see
Technical specifications (Page 53))
Once the fault has been eliminated,
the F-module must be removed and
inserted or the power switched OFF
and ON
Correct the parameter assignment.
Check supply voltage L+ at
BaseUnit
Check BaseUnit type
Verify that the coding element is
present or replace the coding element.
Check the parameter assignment of
the PROFIsafe driver and the address
setting of the F-module.
Check the parameter assignment of
the PROFIsafe driver.
47