6.2 安装 Installation
请安装于金属等阻燃物上。断路器可垂直安装,也可以水平安装。Please install the breaker on
flame retardants such as metal, etc. It can be installed vertically or horizontally.
产品垂直安装时,安装面与垂直面的倾斜角度≤±22.5°。When the product is installed vertically,
the angle of inclination between the installation surface and vertical surface shall be ≤±22.5°.
Fig.14.1 Vertical installation
7 附件说明 Accessory
7.1 分励脱扣器 Shunt release
根据引出的导线编号接入电源(直流电源不必区分正负极) 。当分励脱扣器的外加电压介于额定控
制电源电压 120VAC 的 70%-110% 之间时,能可靠分断断路器。
Power supply is connected to the shunt release according to outlet wire number (no need to
distinguish positive and negative for direct current). At rated control supply voltage of 70%-110%,
shunt release should be reliable to trip breakers.
Fig.15-1 Wiring diagram of Under-voltage release
shunt release
7.2 辅助触头 Auxiliary contact
7.3 辅助触头接入相应外围控制电路 Peripheral control circuits of connection of auxiliary contacts
Table 17 Status indication of auxiliary contact and alarm contact
附件名称
Accessory name
NDT2920214
Edition
图 14.1:垂直安装
表 17:辅助触头状态指示表
断路器状态
Status of the breaker
第 2 版
版次
Version2
图 14.2:水平安装
Fig.14.2 Horizontal installation
图 15-2:分励脱扣器接线图
Connection status of the circuit
9
实施日期
Implementation date
Fig.15-2 Wiring diagram of
2019.12.26