4.6

Securing the burner to the boiler

Detach the combustion head from the burner, (Fig. 12):
 disconnect the oil pipes by unscrewing the two connectors 6);
 loosen the 4 screws 3) and remove the cover 1);
 disengage the swivel coupling 14) from the graduated sector;
 remove the screws 2) from the slide bars 5);
 remove the 2 screws 4) and pull the burner back on slide bars
5) by about 4";
20097599
4.7

Combustion head calibration

RLS 160/E (Fig. 13)
At this point check, whether the maximum delivery of the burner in
2nd stage operation is contained in area A) or in area B) of the firing
rate. See "Firing rates" on page 9.
If it is in area B) then no operation is required.
If, on the other hand, it is in area A), pre-set the combustion head
as below indicated:
 remove the screw 1)(Fig. 13) and extract the internal part 2);
 replace the 4 circular sectors 3) by unscrewing the relevant
screws, with the circular sectors supplied with the burner.
20095042
Installation
 install the extension bars 31)(Fig. 6, page 12) and re-screw
 disconnect the electrode wires and then pull the burner com-
1
2 15 5
3
20
GB
the screws 2) including the safety plate 15);
pletely off the slide bars.
9
4"
8
3
6
14
4
7
Do not remove the circular sector 4.
WARNING
D10525
12
11
10
L
13
Fig. 12
Fig. 13