Usb Data Transfer - Sinclair SCV-EB Series Service Manual

Air-cooled mini chiller unit
Table of Contents

Advertisement

6 USB data transfer

6.1 Parameters setting transfer between wired controllers
Installer can quickly copy the wired controller parameter settings from unit A to unit B via USB disk, which save the
time of on-site installation. Steps are as follows:
Step 1:
Plug U disk into the port of hydro PCB of A unit.
"USb" appears on digital display
Step 2:
Select "READ SET PARAMETER" and press "OK" button then rate of progress will appear. When the process is finished,
"SUCCESS" appears below and an EXCEL file which can not be seen in the wired controller interface but users can find it on
computer will be generated inside the USB disk.
Select "READ SET PARAMETER"
USB FUNCTION
READ SET PARAMETER
WRITE SET PARAMETER
CONFIRM
After that, if parameter correction is needed, please connect the USB with computer and open the EXCEL file to change
parameters and then save it. Please do not change the file name or format. Parameters are not allowed for
non-professionals to change and Sinclair recommends to use the wired controller to change the parameters.
Step 3:
Plug USB disk into the port of hydro PCB of B unit and select "WRITE SET PARAMETER" then rate of progress will appear.
When the process is finished, "SUCCESS" appears below.
Select "WRITE SET PARAMETER"
USB FUNCTION
READ SET PARAMETER
WRITE SET PARAMETER
CONFIRM
86
USB port
USB FUNCTION
63%
READ SET PARAMETER
WRITE SET PARAMETER
CONFIRM
25%
Wired controller interface automatically changes
USB FUNCTION
READ SET PARAMETER
WRITE SET PARAMETER
CONFIRM
Finished
SUCCESS
USB FUNCTION
READ SET PARAMETER
WRITE SET PARAMETER
CONFIRM
EXCEL generated
Finished
SUCCESS