During heating operation, the four-way valve is on; during cooling and defrosting operations, the four-way valve is off.
4.6 Electronic expansion valve control
The position of the electronic expansion valve (EXV) is controlled in steps from 0 (fully closed) to 480 (fully open/standby
position).
 At power-on:
 The EXV first closes fully, then moves to the standby position.
 After the compressor runs, the EXV is controlled according to suction superheat, discharge temperature,
pressure and compressor speed.
 When the outdoor unit is in standby:
 The EXV is at standby position.
 When the outdoor unit stops:
 The EXV first opens fully and remains for 30 seconds, then closes fully, then moves to the standby position.
4.7 Outdoor fan control
The speed of the outdoor unit fan is adjusted in steps, as shown below
Fan speed index
5kW
W1
200
W2
250
W3
300
W4
350
W5
400
W6
450
W7
470
W8
530
W9
550
W10
W11
W12
7kW
200
250
300
350
400
450
470
530
550
/
590
/
650
/
/
Fan speed (rpm)
9kW
12kW
200
200
250
250
300
300
350
350
400
400
450
450
470
530
530
600
550
650
590
730
650
780
/
/
14kW
16kW
200
200
250
250
300
300
350
350
400
400
450
450
530
530
600
600
650
650
730
730
780
780
820
820