Sinclair SCV-EB Series Service Manual page 69

Air-cooled mini chiller unit
Table of Contents

Advertisement

5.23 P3 Troubleshooting
5.23.1
Digital display output
5.23.2
Description
 Compressor current protection.
 Error code is displayed on the refrigerant system PCB digital tube and user interface..
5.23.3
Procedure
High pressure switch protection
The power supply is abnormal
Replace refrigerant system PCB
Notes:
1.
Set a multi-meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
2.
The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
P3
No
No
Yes
Refer to P1 trouble shooting
Yes
Check the power supply equipment
67