5 Press the E MODE button to designate the refrigerant address/unit number.
[--] will flash in the mode number (I) display momentarily.
6 Press the F buttons to set the mode number (I) to 26.
7 Press the G button and the current set setting number (II) will flash.
Use the F button to switch the setting number in response to the external static
pressure to be used.
Internal dry mode
Setting no. of mode no. 26
Disabled
Fan mode for 30 minutes
Fan mode for 60 minutes
8 Press the MODE button E and mode and the setting number (I) and (II) will
change to being on constantly and the contents of the setting can be confirmed.
9 Press the B and H buttons simultaneously for at least two seconds. The
function selection screen will disappear momentarily and the air conditioner
OFF display will appear.
2) For wireless remote controller [Fig. 8-23] (P.12)
1 Press the
button 1 to stop the air conditioner.
• If the weekly timer is enabled (
disable it (
A is off).
2 Press the
button 3 for 5 seconds.
B comes on and the unit enters the self-check mode.
3 Press the
button 4 to set the displayed number D to "50".
• While pointing the wireless remote controller toward the receiver, press the
button 5. (The unit number blinks.)
4 Press the
button 4 to set the unit number of the indoor unit.
• While pointing the wireless remote controller toward the receiver, press the
button 5. (The mode number blinks.)
• When the unit number is transmitted, the selected indoor unit starts operating
in the fan mode.
You can use this step to confirm which indoor unit corresponds to the unit
number you selected to change the functions.
However, if you set the unit number to "00" or "AL", all of the indoor units in
the same refrigerant system will start operating in the fan mode.
• If you transmit a unit number that cannot be selected, the beeper sounds 3
times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)".
If this occurs, press the
while the unit number display is blinking.
• If the signal was not received correctly, the beeper will not sound or it will
beep twice.
If this occurs, press the
while the unit number display is blinking.
3) Changing the power voltage setting (Function table 1)
• Be sure to change the power voltage setting depending on the voltage used.
Function table 1
Select unit number 00
Mode
Power failure automatic recovery*1
(AUTO RESTART FUNCTION)
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Auto mode
Function table 2
Select unit numbers 01 to 04 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
External static pressure
High power fan speed mode
1
2
3
A is on), press the
button 2 to
button 6, and then set the unit number again
button 6, and then set the unit number again
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240V
220V, 230V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled
Settings
100 Hr
2500 Hr
No filter sign indicator
External static pressure
35 Pa
50 Pa (before shipment)
70 Pa
100 Pa
125 Pa
Disabled
Enabled
5 Press the
button 4 to set the mode number.
• While pointing the wireless remote controller toward the receiver, press the
button 5. (The setting number blinks.)
At this time, the beeper sound and OPERATION INDICATOR lamp blinking
pattern indicate the current setting number for the selected mode number.
Current setting value = 1: Beep (1 sec.) x 1 time
= 2: Beep (1 sec.) x 2 times
= 3: Beep (1 sec.) x 3 times
• If you enter a mode that cannot be set, the beeper sounds 3 times
continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)".
If this occurs, press the
again while the mode number display is blinking.
• If the signal was not received correctly, the beeper will not sound or it will
beep twice.
If this occurs, press the
again while the mode number display is blinking.
6 Press the
button 4 to select the setting number.
• While pointing the wireless remote controller toward the receiver, press the
button 5. (The mode number blinks.)
At this time, the beeper sound and OPERATION INDICATOR lamp blinking
pattern indicate the setting number for the selected mode number.
Current setting value = 1: Beep (1 sec.) x 1 time
= 2: Beep (1 sec.) x 2 times
= 3: Beep (1 sec.) x 3 times
• If you enter a number that cannot be set, the originally set number will be
used.
• If the signal was not received correctly, the beeper will not sound or it will
beep twice.
If this occurs, repeat the procedure from step 5.
7 To set another mode without changing the unit number of the indoor unit, repeat
steps 5 and 6.
8 To change the unit number of the indoor unit and perform the function selection,
repeat steps 4–6.
9 Press the
button 1 to complete the function selection.
Note:
• After the function selection is complete, do not operate the wireless
remote controller for 30 seconds.
• Whenever the function selection is used to change the indoor unit
functions after installation, be sure to record all of the settings with a
"○" or other mark in the "Initial setting" column of the table.
Mode no
Mode no
Setting no. of
Setting no. of
mode no. 08
mode no. 10
2
1
3
1
1
2
2
2
3
2
button 6, and then set the mode number
button 6, and then set the mode number
Setting no.
Initial setting
1
 (*1)
01
2
1
02
2
3
1
03
2
3
1
04
2
1
05
2
Setting no.
Initial setting
1
07
2
3
1
08
2
3
1
10
2
3
1
23
2
Check
Check
23