11.4.3 Auto fan at cooling mode:
Room temp. up
Room temp. down
11.4.4 Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
11.4.5 Current protection
Current up
Current down
11.4.6 Rated capacity test
Set mode to cooling mode
Set temp. to 17°C
Set fan speed to high speed
Push turbo button 5 times in 10 seconds.
Using special remoter controller
After 5 hours, cancel rated capacity test
Turbo function
Increasing frequency of compressor
After operating 30 minutes, return automatically to the mode and temp. previously selected.
11.5. Dehumidifying mode
11.5.1 The 4-way valve is off
11.5.2 The indoor fan is fixed in breeze speed
11.5.3 Compressor run in low frequency
11.5.4 Low room temperature protection:
11.5.5 When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor
fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to over
12℃.
11.5.6 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as
that of cooling mode.
11.6. Heating mode
11.6.1. Generally, the 4-way valve is open at heating mode, but it is closed at defrosting. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
11.6.2. Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost.
11.6.3. Action of compressor and outdoor fan motor at heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still valid.
23
Service manual
Condition
T=Indoor Temp.-Setting Temp.
T<1.5℃
1.5℃<T<4℃
T>4℃
T> 3℃
1℃<T<3℃
T<1℃
Evaporator Temp.
0℃<T< 4℃
T< 0℃
Model
Current
MSH-18HRIN1
I>18 A
14.5A<I<18A
I< 12.0A
MSH-18HRIN1
I>17.5 A
14.0A<I<17.5A
I< 11.5A
Indoor fan speed
Compressor
Decrease frequency of compressor
Off
Compressor
Off
Decrease frequency of
compressor
On
Off
Decrease frequency of
compressor
On
Low
Mid.
High
High
Mid.
Low