B. Clearances to Combustibles
32-1/8 in
(816mm)
USA 18-1/8 in (460mm)
CANADA
22-1/8 in (562mm)
NOTE: If trim measurement is over 3/4 in (19mm) in depth
use mantle or side clearance to combustibles.
44-1/8 in
44-1/8 in
1121mm
1121mm
(See next page for thermal protection
In Canada a full length 6 inch (152mm) S635 flue liner required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm) diameter flue liner is required as per UL 1482.
WARNING
Fire Risk.
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
10
TOP TRIM
22-5/8 in
(575mm)
HEARTH
EXTENSION
12in max
12in max
MANTEL
USA 23-1/8 in (587mm)
USA 23-1/8 in (587mm)
CANADA 25-1/8 in (638mm)
CANADA 25-1/8 in (638mm)
HEARTH EXTENSION
requirements)
United States and Canada (UL and ULC)
42-1/8 in
(1070mm)
Minimum Opening
Dimensions
A
Height
Front Width (Steel
Surround)
B
Front Width (Cast Trim
Steel Surround)
C
Back Width
Depth (Steel Surround)
D
Depth (Cast Trim Steel
Surround)
NOTE: Minimum opening dimensions include a 1/4" (6mm)
clearance around unit.
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
7045-910I
A
D
C
B
Inches
21-3/4
30-1/4
30-1/4
24-1/4
16-1/2
16-1/2
January 10, 2020
Millimeters
552
768
768
616
419
419