Parameters List; Outdoor Reset - Bosch BUDERUS SSB120 Installation And Service Instructions For Contractors

Gas condensing stainless steel boiler
Hide thumbs Also See for BUDERUS SSB120:
Table of Contents

Advertisement

36 | Commissioning (for single application)
Selecting "Boiler Status" and pressing "OK" for the following values:
• Flow Temperature
• Return Temperature
• DHW Temperature [Sensor must be connected to show a value. If
not, the default value will appear]
• Outside Temperature
• Flue Temperature [Sensor must be connected to show a value. If not,
the default value will appear]
• System Temperature [Sensor must be connected to show a value. If
not, the default value will appear]
• Fan Speed
• Ionization
• State
• Error
The display shows four lines at a time:
Boiler Status
Flow Temperature
Return Temperature
DHW Temperature
Outside Temperature
Fig. 64
Using the "UP/Down" button it is possible to scroll list.
5 .5

Parameters list

To have access to the parameter list press "menu" button and select
"Settings" using the UP/DOWN button:
Menu
Domestic Hot Water
Information
Settings
System Test
Fig. 65
Press the "OK" button and select "Boiler Settings" using the UP/DOWN
button.
Settings
General Settings
Boiler Settings
Fig. 66
6720818456 (2018/06) US
Press the "OK" button. At this point is request a password [Password is
required for boiler settings only]:
Password
Fig. 67
Enter one digit at a time using the UP/DOWN button to increase/decrease
the value. When the value is correct then press "OK".
In the system there is a password for the three levels:
• Level 1: (no password needed i.e. password N° 0000) USER
• Level 2: (password "0300") INSTALLER
115.0 °F
5 .6
110.0 °F
To set the outdoor reset curve enter in "Central Heating (CH)" menu and
111.0 °F
press "OK".
The display will appear as follow:
50.0 °F

Outdoor reset

Fig. 68
Des. Supply T and Des. Outd T will be highlighted to change either value
press "OK":
• Use up/down arrows to change the Des. Supply T. Use the left/right
arrows to change the Des Outd. T
Repeat steps 1 thru 3 to make additional changes
Once set the parameters press "Esc" to exit the menu.
0
* * *
Outdoor reset
194
32
5
95
T_Outside [°F]
2 Press ok to save changes
3 Use the left/right arrows to select the other values
Des. Supply T.
180°F
Bas. Supply T.
104°F
WW Shutdown
70°F
Bas. Outd. T.
70°F
Des. Outd. T.
25°F
SSB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Buderus ssb85Buderus ssb160