Below is a list of parameters:
Number
Description
3
CH Setpoint
19
Design Supply Temp
21
Baseline Supply Temp
48
DHW/Tank Setpoint
64
Preheat Mode
72
Permit emergency mode
Tab. 12 Level 1 parameters
Number
Description
1
Central Heating (CH) Mode
2
Pump Mode
4
System Pump Overrun
5
Boiler Pump Overrun
7
CH Hysteresis
9
Anti Cycle Period
10
Anti Cycle Temp Diff
11
Ramp Delay Step Mod.
14
Max Power CH
15
Min Power CH/DHW
20
Design Outdoor Temp
22
Baseline Outdoor Temp
23
Design Supply Min Limit
24
Design Supply Max Limit
25
Warm Weather Shutdn
26
Boost Temp Increment
27
Boost Time Delay
28
Night Setback Temp.
29
Weather Setpoint
35
DHW Mode
36
DHW Tank Hyst. Down
37
DHW Tank Hyt. Up
38
DHW Tank Supply Extra
42
DHW Priority
43
DHW Max Priority Time
44
DHW Pump Overrun
73
Boiler Address
74
Emergency Setpoint
75
Delay Per Start Next Dep.
76
Delay Per Stop Next Dep.
77
Hyst Down Start Boiler
78
Hyst Up Stop Boiler
79
Max Setp Offset Down
80
Max Setp Offset Up
81
Start Mod Delay Fact
82
Next Boiler Start Rate
83
Next Boiler Stop Rate
84
Boiler Rotation Interval
85
DHW Boiler Assign
Tab. 13 Level 2 parameters
SSB
Unit
Default
°C / °F
176 °F
°C / °F
176 °F
°C / °F
104 °F
°C / °F
120.2 °F
-
Comfort
-
Yes
Unit
Default
-
1
-
0
Seconds
300
Seconds
300
°C / °F
5.4 °F
Seconds
180
°C / °F
12.6 °F
On / Off
Disabled
%
100
%
1
°C / °F
24.8 °F
°C / °F
69.8 °F
°C / °F
68 °F
°C / °F
194 °F
°C / °F
69.8 °F
°C / °F
0 °F
Minutes
20
°C / °F
18 °F
°C / °F
68 °F
-
0
°C / °F
7.2 °F
°C / °F
0 °F
°C / °F
54 °F
-
0
Minutes
30
Seconds
15
-
0
°C / °F
113 °F
Seconds
15
Seconds
15
°C / °F
9 °F
°C / °F
3.6 °F
°C / °F
7.2 °F
°C / °F
18 °F
Minutes
5
%
80
%
30
Days
1
-
0
Commissioning (for single application) | 37
Min
Max
68 °F
194 °F
68 °F
194 °F
68 °F
194 °F
104 °F
140 °F
Eco
Comfort
No
Yes
Min
Max
0
5
0
4
0
900
0
900
0
36 °F
10
900
0°F
36 °F
50
100
1
30
-13 °F
77 °F
35.6 °F
86 °F
39.2 °F
179.6 °F
80.6 °F
194 °F
35.6 °F
95 °F
0 °F
54 °F
1
120
0 °F
90 °F
32 °F
122 °F
0
2
0 °F
36 °F
0 °F
36 °F
0 °F
54 °F
0
2
1
255
0
255
0
16
68 °F
149 °F
5
300
5
300
0 °F
36 °F
0 °F
36 °F
0 °F
36 °F
0 °F
36 °F
0
60
10
100
10
100
0
30
0
16
6720818456 (2018/06) US
Step
0.9 °F
1.8 °F
1.8 °F
0.9 °F
-
-
Step
1
1
10
10
0.9° F
10
0.9° F
1
1
1.8 °F
1.8 °F
1.8 °F
1.8 °F
1.8 °F
0.9 °F
1
0.9 °F
0.9 °F
1
0.9 °F
1.8 °F
0.9 °F
1
1
1
1
0.9 °F
5
5
0.9 °F
0.9 °F
0.9 °F
0.9 °F
1
1
1
1