Kidde DC-9102E-KID Quick Start Manual page 2

Conventional photolectric smoke detector

Advertisement

Note: To operate correctly, the DC-9102E-KID must be connected to a compatible fire alarm control panel. Connecting
the smoke detector directly to 24VDC will damage the detector.
By default, the detector is set to sensitivity level 1 and LED status is 'ON', which can be modified by using a P-9910B programmer.
Programming or reading the detector: Connect the handheld programmer to the heat detector terminals '1' and '3' using the
clips provided.
Unlocking the Programmer: Turn the programmer on and enter the unlock pin '456' and press 'clear' a '0' should appear on the
LCD.
Program sensitivity: To change the sensitivity, press the 'Function' key followed by '3'. A '-'should appear on the LCD. Enter: '1'
for Smoke Sensitivity 1, '2' for Smoke Sensitivity 2, followed by the 'Program' button. Once complete, there will be a 'P' shown on
the LCD, indicating its class is programmed.
Read Detector Sensitivity: When the programmer is in a standby state, press the 'Test button'. 'L' will appear followed by an
Address for the Detector. Pressing 'Up' will scroll through the Detector sensitivity level, device type and heat detector class. For
these Conventional Smoke Detectors the Detector Address is not applicable.
Locking the Programmer: press 'Clear' and enter locking pin '789' followed by 'Clear' to exit.
When the detector is connected to the KID1xxA conventional FDCIE or an addressable zone monitor unit, a 4.7kΩ end of line
resistor is to be fitted at the last DB-01 base on the circuit. See Fig. 5.
Testing
FIGURE 6
Page 2 of 3
Table 1 Parameters Setup
Parameter
Smoke Sensitivity
1
2
FIGURE 5
Note: Before testing, Ensure the detector is properly installed and powered up.
Testing can only commence after the detector is powered up for a minimum 10
seconds.
The detector must be tested after installation and regular maintenance as per local code.
The two methods are as follows:
(1) Reed switch testing
Place the commission tool on the testing area of the detector as shown in Fig. 6,
hold for several seconds until the detector is in alarms.
(2) Smoke test
Apply the detector smoke tester to the detector until it alarms.
On completion of test, reset the detector at the FDCIE.
If a detector fails during testing, follow the steps outlined in the Maintenance section,
and retest it. If it still fails, replace the detector .
Polling LED Status
1
ON
2
ON
DC-9102E-KID
D A T A S H E E T
Issue 1.0